DOL 534 • DOL 539 Climate Controller User Manual English: For other language variants of this document we refer to: Español: Para otras variantes del idioma de este documento, visite: Français: Pour les versions dans d'autres langues de ce document veuillez consulter: http://docs.skov.com/1017...
Page 3
It was released in 2017. Product and Documentation Changes SKOV A/S reserves the right to change this manual and the product described herein without further notice. In case of doubt, please contact SKOV A/S. Date of change appears from the front and the back page.
If a function is not used, e.g. Extra sensor, it is not shown on the controller's user menus. The manual can therefore contain sections that are not relevant to the specific set-up of your controller. See also Technical Manual or, if necessary, contact SKOV A/S service or your dealer. This manual's User Guide consists of a general introduction, which describes briefly how to operate the house controller.
It is also possible to select predefined front views, in which the selected values and displays are customised for different animal types. Press and select Front view configuration/ Load default front views. DOL 534 • DOL 539...
Enter the morning and evening numbers of animals added or removed. The total number is reset at the beginning of every day (midnight). See also section Error! Reference source not found.. DOL 534 • DOL 539...
There is also quick access to change the displayed settings by pressing the tool-tip Ventilation requirement Displays the parameters that affect the current ventilation. In this example, ventilation is based exclusively on temperature. DOL 534 • DOL 539...
(max. 5 in total). The same function can also be selected to displays on several pages, if this is required Press to proceed to the next step. Press to go back to the previous page DOL 534 • DOL 539...
A blue mark on the bar displays the change. Press to implement the change. Press to undo. Press to be given the option of entering the setting using the numeric keypad. DOL 534 • DOL 539...
Deactivated alarms are grey. The alarm relay is only trigged by hard alarms. Soft alarms generate a pop-up in the display. See also section 5. Selection of Language Select Selection of language and highlight the desired language. DOL 534 • DOL 539...
Place house controller in manual mode Service Daily + advanced + service: 3333 Changing of settings under Technical menu SKOV A/S recommends that you change the passwords of the factory setting and subsequently change the password on a regular basis. DOL 534 • DOL 539...
User Manual Climate This menu provides access to set and read values for the ventilation system's components. Type of ventilation In this menu, DOL 53X shows the type of ventilation that the system is currently operating. DOL 534 • DOL 539...
Min./max. temperature tunnel Tunnel temperature minimum TUNNEL Tunnel temperature minimum time Tunnel temperature maximum Tunnel temperature maximum time Min./max. temperature outside Outside temperature min. Outside temperature min. time Outside temperature max. Outside temperature max. time DOL 534 • DOL 539...
Page 18
Comfort temperature Advanced Comfort Extra ventilation SIDE No heatwave detected Heatwave comfort Heatwave comfort active Outside temperature limit Activation time Day-and-night adjustment Temperature Start time Stop time Table 1: Overview of the complete Temperature menu. DOL 534 • DOL 539...
If you want to change the temperature with the same number of degrees in both zones, you can change through the curve. DOL 534 • DOL 539...
Page 20
Set heating offset In houses with heating systems, DOL 53X regulates the inside temperature according to the set temperature, , and according to a lower temperature limit, Temperature Absolute heating temperature DOL 534 • DOL 539...
Page 21
, set the temperature which is the lowest temperature allowed at the heater in question. Stand-alone heater When the inside temperature is lower than this setting, the heater supplies heat. DOL 534 • DOL 539...
Highest temperature during the last 24 hours and the time of occurrence are stated for Max. 24h all temperature measurements. Lowest/highest temperature during the last 24 hours at the individual sensor. Sensor min/max The current temperature at the individual sensor. Individual temp. sensor DOL 534 • DOL 539...
The controller will not turn off the heating system again until the outside temperature exceeds Outside temperature below by more than 2° C. This prevents the heating system from connecting and disconnecting continuously when the outside temperature fluctuates around the set temperature. DOL 534 • DOL 539...
Without a sensor, the controller will supply heat with a set percentage of the floor heating system's capacity. 3.2.5.1 Floor Heating with Temperature Sensor Display of current floor temperature. Floor temperature The set floor temperature Floor temperature setpoint DOL 534 • DOL 539...
Page 25
When floor heating is installed without a temperature sensor, the temperature is regulated via a curve over the course of the batch. 3.2.5.3 Shared Parameters (with and without Sensor) Current supply of floor heating in per cent. Floor heating requirement DOL 534 • DOL 539...
Setting of how many degrees the inside temperature will change by in terms of the Day and night adjustment (see section 3.2.6.3). Temperature setpoint The time at which the function starts. Start time Stop time DOL 534 • DOL 539...
Page 27
Control parameters Comfort Comfort ventilation At batch production, the comfort temperature can be set as a curve equating to a time span of two day numbers. Ventilation can thereby be increased when the animals get larger. DOL 534 • DOL 539...
Page 28
Extra ventilation is activated when the inside temperature is over Temperature setpoint Comfort temperature, and ventilation is already at maximum. DOL 53X gradually increases the additional ventilation. DOL 534 • DOL 539...
Page 29
Day and night adjustment is intended for changing the inside temperature over 24 hours in order to support the animal's normal behaviour. A lower inside temperature will make the animals experience a normal circadian rhythm. Furthermore, the ventilation level will be relatively higher, thus ensuring a better air quality. DOL 534 • DOL 539...
Page 30
In batch production mode, the function can be set to lower the temperature automatically during the processing of the batch. See the menu to set a curve for Management/ Batch curves/ Climate Day and night adjustment DOL 534 • DOL 539...
When air humidity is lower than the setting, the controller first reduces ventilation and then activates humidification if the house has a humidification system. DOL 534 • DOL 539...
Page 32
Active Selecting type of humidity control. See section 3.3.2.1, 3.3.2.2 and 3.3.2.3. Humidity control mode In the case of humidity ventilation. Setting of the degree of ventilation where the Max. humidity ventilation humidity ventilation stops. DOL 534 • DOL 539...
5%. If the temperature falls so much that the relative air humidity reaches 100%, the water vapour will start to condense (dew point). Climate/ Humidity/ Active When humidity control is disconnected, DOL 53X regulates ventilation according to the inside temperature alone. DOL 534 • DOL 539...
Page 34
At a lower temperature setting, DOL 53X will thus increase ventilation and consequently the change of air. When this has made the inside temperature drop, ventilation will decrease to minimum ventilation in order to limit the heat loss from the ventilation. DOL 534 • DOL 539...
Page 35
Humidity heat makes it possible to keep the house air humidity at the set humidity. Check the heat consumption at regular intervals when using the principle of humidity heating to regulate the house humidity. Settings for heating and humidity control should be checked to avoid excessive heating costs. DOL 534 • DOL 539...
The heat recovery unit has two fans. One of the fans removes warm, humid air from the house. The other fan draws fresh, preheated air into the house. DOL 534 • DOL 539...
Page 37
Error! Reference source not found.. unit Setting degrees. When the outside temperature is closer to the temperature Disable heat recovery unit below setpoint than the set degrees, the heat recovery unit disconnects. Also see set point Example 14. DOL 534 • DOL 539...
Page 38
Setting of number of cleaning programs per 24 hours. Setting for each cleaning program at the time when cleaning is to run and the time at which it will stop. Current status Status views of the heat recovery unit's individual parts. Info DOL 534 • DOL 539...
Page 39
Minimum ventilation ventilation level that is too low or two high. It is therefore also important that the setpoints for are correct even if CO minimum ventilation is used. Minimum ventilation Number of animals DOL 534 • DOL 539...
Page 40
Too low a setting can result in a very high heat consumption or temperature drop in the livestock house, if there is no heat supply available. Also see paragraph 5.4for a description of the NH alarm. DOL 534 • DOL 539...
Ventilation requirement Air total Dynamic Air, stepless Air outlet High/Low FreeRange Closed/open Minimum ventilation Humidity ventilation Maximum ventilation Ventilation status Cycle timer minimum inlet Cycling stopped Next change: Cycle timer air outlet Cycling stopped Next change: DOL 534 • DOL 539...
Page 42
Temperature setpoint Temp. deviation in relation to which DOL 53X adjusts the shutter position of the air inlets. Also, see section 3.7.3. Factor for zone regulation of the air inlet flap position. Inlet correction factor DOL 534 • DOL 539...
/h) per animal. You can find the correct figure in the technical literature or ask your adviser if in doubt. Please note that the correct number of animals must be set in the menu. Production/ Animals See also section 4.4 regarding batch curves. DOL 534 • DOL 539...
, the shutter position will be Temperature setpoint adjusted with this factor in relation to the extent of the deviation. The higher the factor is set, the more the shutter position is adjusted. Also, see example in Technical manual. DOL 534 • DOL 539...
When FreeRange is active, the temperature setpoint and the heat setpoint are adjusted with an offset in relation to the general settings. If the inside temperature becomes too high or too low, DOL 53X will adjust with ventilation or heat supply as normal. Alarm limits are also adapted. DOL 534 • DOL 539...
De-icing disconnects again Outside temperature -10 °C below Outside temperature °C You must set Outside temperature below to the number of degrees to which the outside temperature can fall before DOL 53X activates the de-icing function. DOL 534 • DOL 539...
The reading shows how big a percentage of the high- pressure cooling system's capacity that is currently active. This feature is particularly useful in hot and dry areas where high-pressure cooling will run alternately to the humidification, respectively to cool and increase humidity. DOL 534 • DOL 539...
Setting of the time that must elapse from when side cooling was last active to when Nozzle cleaning time the nozzle cleaning function will run. Setpoint of the time when side cleaning shall operate. Nozzle cleaning interval DOL 534 • DOL 539...
Air speed requirement Air speed Possible max. air speed User limited max. air speed Chill effect Tunnel status Cycling stopped Next change: Tunnel inlet Stepless tunnel Tunnel MultiStep 1 Table 6: Overview of the complete Tunnel menu. DOL 534 • DOL 539...
Page 51
Display of the calculated air speed in the house. Air speed Reading the systems maximum air speed. Possible max. air speed Reading the system set maximum air speed.( Max. Air speed User limited max. air speed DOL 534 • DOL 539...
DOL 53X calculates the current cooling effect on the basis of the air speed in the house and the current chill factor. Example 18: Chill factor and chill effect Full-grown animals Day-old chickens Air speed 1.5 m/s 1.5 m/s Chill factor Chill effect 4.5° C 12° C 30° C feels like 25.5° C 18° C DOL 534 • DOL 539...
The current air speed is a calculated value (metres/sec.). The climate and production controller calculates the current air speed through the house based on the cross-sectional area (m ) and the current capacity of the tunnel fans. DOL 534 • DOL 539...
Setting of the air speed that starts tunnel cooling. Start air speed The number of degrees that is felt in terms of temperature - at maximum tunnel Start temperature ventilation - must exceed , before the tunnel cooling starts. the temperature set point DOL 534 • DOL 539...
Page 55
Reading of how many times the cooling has been started yesterday. Number of starts yesterday Selecting which factor is to activate tunnel cooling. ( Temperature/ Air speed Start based on: DOL 534 • DOL 539...
Connection and disconnection of pressure control in tunnel ventilation. Active in tunnel mode The current pressure level in the house. Pressure sensor An indication (percentage) of how much the flaps are to be open to maintain the Calculated air inlet Pressure setpoint DOL 534 • DOL 539...
DOL 53X can be connected to up to four auxiliary sensors. The display of the menu depends on Aux. sensors which types of auxiliary sensors you install. Current value registered by the sensor. Aux. sensor (x) DOL 534 • DOL 539...
Table 10: Overview of the complete Stir fan menu. A stir fan improves circulation of the air and thus provides a more uniform temperature in the house. DOL 53X can regulate up to four stir fans at a time. DOL 534 • DOL 539...
Stir fan diff. temp. sensors. Example 20: Temperature sensor regulation Temperature Stir fan temp. 2° C ON time 5 min. Stir fan temperature OFF time 5 min. Temp. setpoint Time DOL 534 • DOL 539...
This function is active only when heating is required. Example 21: Heat source regulation Way to control: With heater Stop delay Heater Stir fan Start delay Way to control: After heater Start delay ON time Time DOL 534 • DOL 539...
Maximum air speed Tunnel cooling start air speed Tunnel cooling stop air speed Day-and-night temperature Table 12: Overview of the complete user-offset menu Viewing the current user offset to the standard curve values. User- offsets DOL 534 • DOL 539...
Water/ bird yesterday Water/feed Water/feed yesterday Mortality Bird weight Bird weight yesterday Weight of all birds Trend curves Climate Temperature Tunnel temperature Humidity Outside humidity Outside temp. CO2 sensor NH3 sensor Pressure sensor Tunnel cooling temperature DOL 534 • DOL 539...
Page 63
Moved animals Investigated animals Breeders Added animals Breeders Trend curve 24 h Power monitoring Power monitor 1-2 Trend curve 50 days Batch curves Climate Inside temperature Heat offset temperature Comfort temperature Stand-alone heater temperature Floor heating DOL 534 • DOL 539...
Page 64
Drying time Disinfection Disinfection time Temperature Empty house Roof inlet flap Roof inlet fan Re-circulation inlet Side inlet Tunnel inlet Ventilation Air outlet flap Air outlet fan speed Heating Preheating setpoint Preheating at batch stop DOL 534 • DOL 539...
Day number can be set to -9 so DOL 53X can control the preheating of the house prior to the birds being stocked (also see section 4.1.1.1). Display of current week number. Week number Stocked animals DOL 534 • DOL 539...
If, on the other hand, you want the system to close when the batch status is empty house, reset the settings in the in-between function empty house. In the Empty house batch status, DOL 53X will also reset any changes of curves which you have made during the previous batch course. DOL 534 • DOL 539...
Set up a plan for naming all controllers connected to the network. Key Values Display of production values. Trend Curves Climate trend curves give a picture of how the climate has developed during the last 24 hours. DOL 534 • DOL 539...
1) a day number for each of the up to eight curve points. 2) the required value of the function of each of the up to eight curve points. See also section 3.15 regarding user offsets. DOL 534 • DOL 539...
(in the menu Empty house Management House data Batch status The menu is visible only when the batch status is Empty house. Example 23: In-between function at batch production Batch 1 Batch 2 DOL 534 • DOL 539...
Page 70
Setting the period in which the soaking system is running. Washing time Setting the active period for washing. Heating Setting the heating in connection with the function. Drying Drying time Setting the active period for drying. DOL 534 • DOL 539...
While washing the house manually, ventilation must run again to start changing the air in the house. 4.5.3 Drying Drying is a combination of ventilation and heating. The more heat you supply to the house, the quicker it dries. DOL 534 • DOL 539...
In batch production, the function can maintain an inside temperature of 4°C, for Preheating at batch stop example, between two batches. Note that ventilation must be closed and the heating system must be on. DOL 534 • DOL 539...
Page 73
Preheating at batch stop Day number When the batch state is Empty house Management House data ) and Preheating has been connected, DOL 53X will regulate according to the temperature for Preheating at batch stop DOL 534 • DOL 539...
Setting the time period. The time period should correspond to the time that the Stop feed mix before feed animals should only have one type of feed. weigher is stopped DOL 534 • DOL 539...
Page 75
(non-wheat) Catching key active (animals eat until (animals get the system is only one type of empty) food) Catching automatically ends if not Date/time stopped The sequence when stopping the feed system during Catching. DOL 534 • DOL 539...
For instance, a flap alarm could be succeeded by a temperature alarm as the controller cannot control the temperature correctly with a defective flap. This way, the previous alarms enable you to follow an alarm course back in time and find the error that caused the alarms. DOL 534 • DOL 539...
Soft alarm Low temperature limit - 3 °C Low temp. limit with - 10 °C FreeRange Summer temp. at 20° C/68° 8 °C F outside temp. Summer temp. at 30° C/86° 4 °C F outside temp. DOL 534 • DOL 539...
Page 78
Low CO2 Disconnected Hard Soft Low CO2 limit 300 ppm Disconnected High CO2 Hard Soft 8500 ppm High CO2 limit Low NH3 Disconnected NH3 alarm Hard Soft Low HN3 limit 5 ppm High NH3 Disconnected Hard DOL 534 • DOL 539...
Page 79
16.4 V Emergency inlet Emergency inlet ON/OFF Absolute high temperature 4 °C Error temperature sensor ON/OFF Power failure: ON Power failure alarm: Always ON Alarms maintained Alarm test Table 14: Overview of the Alarm menu DOL 534 • DOL 539...
DOL 53X generates an alarm when the temperature difference between the front and (2 zones) rear zones exceeds the set number of degrees DOL 534 • DOL 539...
Page 81
At an outside temperature of e.g. 25° C, the inside temperature must thus be 6° C higher (exceed 30° C) before the alarm is generated. 4. Above 30° C outside, the alarm limit is staggered 4° C in relation to the outside temperature. DOL 534 • DOL 539...
Page 82
Temperature range where the alarm is generated Outdoor temperature °C The high temperature alarm adjusts for comfort temperatures so that the alarm does not generate until the Comfort temperature has been added to the Temperature setpoint set. DOL 534 • DOL 539...
Page 83
(5 %) that the alarm is only usually triggered upon intrinsic sensor errors. In the case of a high alarm (20 ppm) DOL 53X ventilates 100%. Also see paragraph 3.6 Pressure DOL 534 • DOL 539...
Connect or disconnect Table 15: Release of emergency opening It may be an advantage to disconnect absolute high humidity in houses situated in areas with very high outside air humidity, and if a technical sensor error occurs. DOL 534 • DOL 539...
Page 85
DOL 53X can generate an alarm when the battery which powers the emergency opening does not function. Make sure not to set the too low as this will make the alarm inactive. Battery voltage limit DOL 534 • DOL 539...
Page 86
This setting makes it possible to open the air intake during a hot season where the air intake, under normal conditions, is not activated by the normal high temperature alarm limit. 5.4.1.4 Power Failure Alarm The DOL 53X controller will always generate an alarm in case of power failure. DOL 534 • DOL 539...
See the picture. It will be possible for a customer to deliver SKOV A/S products to local collection sites/recycling stations according to local instructions. The recycling station will then send the products to an approved plant for recycling and reuse.