Samson 3731-3 Mounting And Operating Instructions page 81

3731 series electropneumatic ex d with hart communication
Table of Contents

Advertisement

Data errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
68
Control parameter
Additional alarm at the fault
alarm output
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
Poti parameter
69
Additional alarm at the fault
alarm output
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
70
Calibration parameter
Additional alarm at the fault
alarm output
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
71
General parameters
Status classification [Maintenance required]
Recommended action Confirm error.
72
Start-up parameters
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
73
Internal device error 1
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
74
HART parameters
Status classification [Maintenance required]
Recommended action Confirm error and perform reset.
When fault alarms exist, they are displayed here.
Control parameter error
Parameter error of the digital potentiometer.
Error in the production calibration data. Subsequently, the device
runs on default values.
Parameter errors that are not critical for the control.
Check and, if necessary, reset required parameters.
Start-up parameter error
Internal device error
Parameter errors that are not critical for the control.
Code list
81