Code list
Parameter – Display, values
Code
no.
[default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
4*
Pin position
[No]
17, 25, 35, 50, 70, 100,
200, 300 mm
90° with rotary actuators
ESC
Note: If you select a pin
position in Code 4 that is too
small, the positioner switches
to the fail-safe position
mode (SAFE ) for reasons of
safety.
5*
Nominal range
mm or angle °
ESC
6*
Initialization mode
[MAX]
NOM · MAN · SUB · ZP
ESC
66
EB 8387-3 EN
Description
The follower pin must be inserted into the correct pin position ac-
cording to the valve travel/angle of rotation.
The pin position must be entered for initialization using NOM or
SUB.
Pin position
Code 4
17
25
35
50
70
100
200
90°
For initialization using NOM or SUB, the nominal travel/angle of
rotation of the valve must be entered.
The permissible adjustment range depends on the pin position
according to the table for Code 4.
Code 5 is generally locked until Code 4 is set to No, i.e. after a
pin position has been entered, Code 5 can be configured.
After initialization has been successfully completed, the max-
imum nominal travel/angle reached on initialization is dis-
played.
Select the initialization mode
MAX:
Maximum range of the control valve, the travel/angle of
the closure member from the CLOSED position to the op-
posite stop in the actuator.
NOM: Nominal range of the control valve, the travel/angle of
the closure member measured from the CLOSED position
to the indicated OPEN position.
MAN: Manually selected range
SUB:
Substitute calibration (without initialization)
ZP:
Zero calibration
Standard
Adjustment range
Code 5
Code 5
7.5
3.6 to 18.0
7.5
5.0 to 25.0
15.0
7.0 to 35.0
30.0
10.0 to 50.0
40.0
14.0 to 70.7
60.0
20.0 to 100.0
120.0
40.0 to 200.0
90.0
24.0 to 100.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents