Performance Data - Marstair 600E/M Technical Manual

Table of Contents

Advertisement

PERFORMANCE DATA (kW)
NOTE THAT THERE ARE 3 SPEED RANGES OF LOW, MEDIUM AND HIGH
Range 3 = highest for maxium duties
Range 2 = medium for normal operations
Range 1 = lowest for minimum noise levels
RANGE 3
RANGE 2
RANGE 1
LOW
MCU+
600
or
TOT
SHR SENS TOT
(ALL)
DCU+
20
15
1.77 0.75 1.33 1.82 0.80 1.46 1.87 0.85 1.59 1.91 0.92 1.75 1.94 1.00 1.94 2.13 1.00 2.13 2.05 1.00 2.05
20
20
2.28 0.69 1.58 2.35 0.72 1.70 2.40 0.76 1.83 2.45 0.81 1.99 2.50 0.88 2.19 2.65 0.93 2.47 2.28 1.00 2.28
20
30
N/A*
40
30
3.13 0.67 2.09 3.29 0.68 2.25 3.40 0.71 2.41 3.52 0.74 2.61 3.60 0.79 2.84 3.86 0.81 3.14 3.06 1.00 3.06
40
40
3.50 0.66 2.30 3.69 0.67 2.47 3.84 0.69 2.63 3.98 0.71 2.83 4.09 0.75 3.06 4.27 0.77 3.30 3.84 0.93 3.57
40
50
N/A*
60
40
3.60 0.66 2.39 3.79 0.68 2.58 3.92 0.70 2.76 4.06 0.73 2.98 4.18 0.78 3.25 4.33 0.81 3.52 3.87 0.99 3.84
60
50
4.35 0.65 2.82 4.66 0.66 3.06 4.89 0.67 3.26 5.14 0.68 3.51 5.35 0.71 3.81 5.72 0.72 4.09 4.80 0.88 4.20
60
60
N/A*
* Cannot be used on low speed
Rated at BS2852: Part 1: 1982: UK condition C; NEMA condition A; Tropical condition B
HEAT PUMP
a. Cooling (MAX speed outdoor unit fan)
RANGE 3
RANGE 2
RANGE 1
MHPUL
600 (ALL)
MHPUE
TOT
DHPUE
20
15
1.77 0.75 1.33 1.82 0.80 1.46 1.87 0.85 1.59 1.91 0.92 1.75 1.94 1.00 1.94 2.23
40
30
3.13 0.67 2.09 3.29 0.68 2.25 3.40 0.71 2.41 3.52 0.74 2.61 3.60 0.79 2.84 3.86
60
50
4.35 0.65 2.82 4.66 0.66 3.06 4.89 0.67 3.26 5.14 0.68 3.51 5.35 0.71 3.81 5.72
b. Heating (Room 20°C/12°C, outdoor unit fan at MAX speed)
HEATING OUTPUT AT 7°C AMBIENT
RANGE 3
RANGE 2
RANGE 1
MHPUL
600 (ALL)
MHPUE
DHPUE
20
15
40
30
60
50
Tel: 01823 665660
Heronhill - for all your Marstair requirements
UK CONDITIONS
ROOM 21°C/15°C
AMBIENT 27°C/19°C
LOW
LOW
MEDIUM
MEDIUM
HIGH
SHR SENS TOT
SHR SENS TOT
2.63 0.70 1.84 2.71 0.73 1.97 2.78 0.77 2.14 2.85 0.83 2.35 3.03 0.86 2.61 2.37 1.00 2.37
4.59 0.66 3.01 4.83 0.67 3.22 5.05 0.69 3.47 5.27 0.72 3.78 5.66 0.72 4.08 4.73 0.89 4.20
4.97 0.65 3.24 5.24 0.66 3.45 5.51 0.67 3.71 5.78 0.70 4.02 6.26 0.69 4.32 5.18 0.84 4.36
UK CONDITIONS
ROOM 21°C/15°C
AMBIENT 27°C/19°C
LOW
LOW
MEDIUM
LOW
MEDIUM
HIGH
SHR SENS TOT SHR SENS TOT SHR SENS TOT
(EUROVENT)
LOW
MEDIUM
MEDIUM
HIGH
HIGH
kW
COP
kW
COP
2.06
2.50
2.07
2.52
2.92
2.70
2.98
2.75
5.48
2.48
5.68
2.58
www.heronhill.co.uk
MEDIUM
HIGH
HIGH
SHR SENS TOT
SHR SENS TOT
MEDIUM
HIGH
HIGH
SHR SENS TOTAL SHR SENS TOTAL
HEATING OUTPUT AT -1°C AMBIENT
HIGH
LOW
MEDIUM
HIGH
kW
COP
kW
COP
2.13
2.60
1.58
2.10
3.46
3.23
2.30
2.30
5.71
2.89
4.42
2.31
5/25
EUROVENT
TROPICAL
(NEMA)
ROOM
ROOM
29°C/19°C
27°C/19°C
AMB 46°C/24°C
AMB 35°C/24°C
HIGH
HIGH
SHR SENS TOT
SHR SENS
EUROVENT (NEMA)
ROOM 27°C/19°C
AMBIENT 35°C/24°C
HIGH
SHR
SENS
1.00
2.23
0.81
3.14
0.72
4.09
MEDIUM
HIGH
HIGH
kW
COP
kW
COP
1.68
2.20
1.72
2.23
2.40
2.40
2.60
2.60
4.64
2.31
4.75
2.59
55208033-08