ELECTRICAL DATA

Cooling data rated at EUROVENT (NEMA) conditions 27°C / 19.4°C indoor; 35°/24°C ambient.
Heating data rated at 20°C/12°C indoor; 7°C/6°C ambient
With MCU+
MODEL
COMBINATION
Cooling Heating Cooling Heating
600 (ALL)
MCU+
kW
20
15
1.2
20
20
1.4
20
30
1.7
40
30
1.7
40
40
2.2
40
50
2.1
60
40
2.2
60
50
2.1
60
60
2.5
With DCU+
MODEL
COMBINATION
Cooling Heating Cooling Heating
600 (ALL)
DCU+
kW
20
15
1.4
20
20
1.5
20
30
1.8
40
30
1.9
40
40
2.4
40
50
3.0
60
40
2.4
60
50
3.0
60
60
3.2
With MHPUL/MHPUE
INPUT
MODEL
STD.
COMBINATION
MODEL
600L / E
MHPUL/E
kW
20
15
1.2
40
30
1.7
60
50
2.1
With DHPUE
INPUT
MODEL
STD.
COMBINATION
MODEL
600E
DHPUE
kW
20
15
1.4
40
30
1.8
60
50
2.5
Tel: 01823 665660
Heronhill - for all your Marstair requirements
1 Ph 230V 50Hz
FULL LOAD
INPUT
AMPS
kW
AMPS
AMPS
2.0
6.4
8.3
2.0
7.4
8.3
2.0
8.6
8.3
2.0
8.6
8.3
2.0
10.7
8.3
2.0
9.4
8.3
2.0
10.7
8.3
2.0
9.4
8.3
2.0
10.5
8.3
1 Ph 230V 50Hz
FULL LOAD
INPUT
AMPS
kW
AMPS
AMPS
2.0
6.6
8.3
2.0
7.4
8.3
2.0
9.0
8.3
2.0
9.0
8.3
2.0
11.3
8.3
2.0
11.8
8.3
2.0
11.3
8.3
2.0
11.8
8.3
2.0
15.1
8.3
1 Ph 230V 50Hz
FULL LOAD AMPS
+ELECT
STD.
+ELECT
Heating
MODEL
Heating
kW
AMPS
AMPS
3.1
6.4
14.7
3.4
8.6
16.4
4.1
9.4
17.2
1 Ph 230V 50Hz
FULL LOAD AMPS
+ELECT
STD.
+ELECT
Heating
MODEL
Heating
kW
AMPS
AMPS
3.3
4.9
12.9
3.7
8.9
16.9
4.4
11.8
19.8
www.heronhill.co.uk
SYSTEM
MAX.
INPUT
STARTING
CURRENT
Cooling Heating Cooling Heating
AMPS
kW
kW
23
--
--
28
--
--
37
1.7
2.0
37
1.7
2.0
51
2.1
2.0
59
2.0
2.0
51
2.1
2.0
59
2.0
2.0
63
2.4
2.0
SYSTEM
MAX.
INPUT
STARTING
CURRENT
Cooling Heating Cooling Heating
AMPS
kW
kW
25
--
--
29
--
--
37
1.9
2.0
37
1.9
2.0
51
2.4
2.0
52
2.5
2.0
51
2.4
2.0
52
2.5
2.0
61
3.2
2.0
SYSTEM
INPUT
MAX.
STD.
+ELECT
STARTING
MODEL
Heating
CURRENT
AMPS
kW
kW
24
--
--
44
1.7
3.5
67
2.0
3.8
SYSTEM
INPUT
MAX.
STD.
+ ELECT
STARTING
MODEL
Heating
CURRENT
AMPS
kW
kW
24
--
--
45
1.8
3.7
59
2.5
4.3
8/25
3 Ph 400V 50Hz
SYSTEM
FULL LOAD
MAX.
AMPS
STARTING
CURRENT
A/PH
A/PH*
A/PH
--
--
--
--
--
--
4.1
8.3
19
4.1
8.3
19
5.3
8.3
23
4.7
8.3
27
5.3
8.3
23
4.7
8.3
27
4.7
8.3
33
3 Ph 400V 50Hz
SYSTEM
FULL LOAD
MAX.
AMPS
STARTING
CURRENT
A/PH
A/PH*
A/PH
--
--
--
--
--
--
4.1
8.3
19
4.1
8.3
19
5.2
8.3
24
5.0
8.3
23
5.2
8.3
24
5.0
8.3
23
6.4
8.3
26
3 Ph 400V 50Hz
SYSTEM
FULL LOAD AMPS
MAX.
STD.
+ELECT
STARTING
MODEL
Heating
CURRENT
A/PH
A/PH*
A/PH
--
--
--
4.1
12.2
27
4.7
12.3
35
3 Ph 400V 50Hz
SYSTEM
FULL LOAD AMPS
MAX.
STD.
+ ELECT
STARTING
MODEL
Heating
CURRENT
A/PH
A/PH*
A/PH
--
--
--
4.1
12.1
27
5.4
13.2
32
55208033-08