Gree GWC36LB-D1NNA2A/I Service Manual page 43

Refrigerant r22
Table of Contents

Advertisement

Outdoor
condenser
4
temperature sensor is
open/short-circuited
Outdoor
discharge
5
temperature sensor is
open/short-circuited
High
pressure
6
protection
7
Freeze protection
Low pressure protection
8
of compressor
High discharge
9
temperature protection
of compressor
Communication
10
malfunction
40
OFF
3S
F4
and blinks
4 times
OFF
3S
F5
and blinks
5 times
OFF 3S and
E1
blinks once
E2
OFF 3S and
blinks twice.
OFF 3S and
E3
blinks 3
times.
OFF 3S and
E4
blinks 4
times
OFF 3S and
E6
blinks 6
times
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
compressor stops and indoor fan
operates; During heating operation,
the complete unit stops operation.
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
compressor stops and indoor fan
operates; During heating operation,
the complete unit stops operation.
During cooling and drying operation,
except indoor fan operates, all loads
stop operation. During heating
operation, the complete unit stops; if
it is floor standing unit
During cooling and drying operation,
compressor and outdoor fan stop
while indoor fan operates.
The complete unit stops
During cooling and drying operation,
compressor and outdoor fan stop
while indoor fan operates. During
heating operation, all loads stop.
During cooling operation, compressor
stops while indoor fan motor
operates. During heating operation,
the complete unit stops.
Troubleshooting
1. The wiring terminal between outdoor condenser
temperature sensor and controller is loosened or
poorly contacted;
2. There's short circuit due to the trip-over of the parts
on controller;
3.Outdoor condenser temperature sensor is damaged
(Please check it by referring to the resistance table for
temperature sensor)
4. Main board is broken.
1. The wiring terminal between outdoor discharge
temperature sensor and controller is loosened or
poorly contacted;
2. There's short circuit due to the trip-over of the parts
on controller;
3.
Outdoor
discharge
temperature
damaged.
(Please check it by referring to the
resistance table for temperature sensor)
4. Main board is broken.
1. The main board and the display panel are not
connected well.
2. The OVC terminal on main board is not connected
well with the high pressure switch on the complete
unit.
3. The wiring of high pressure switch is loosened.
4. Refrigerant is superabundant;
5. Poor heat exchange (including blocked heat
exchanger and bad radiating environment );
6. Ambient temperature is too high; (if it is 3-phase
unit, the high pressure protection may be caused by
overcurrent protection due to this reason)
7. The supply voltage is abnormal (if it is 3-phase unit,
the high pressure protection may be caused by
overcurrent protection due to this reason)
8. The air intake and air discharge at indoor / outdoor
heat exchanger are not smooth. The air cycle is short
circuited.
9. Filter and heat exchange fins of indoor/outdoor
units are blocked.
10. The system pipeline is blocked.
1. Poor air-return in indoor unit;
2. Abnormal fan speed;
3. Dirty evaporator;
4. System is normal, but the indoor tube temperature
sensor is abnormal, or the tube temperature sensor is
not connected well.
1. The main board and display panel are not
connected well.
2. The LPP terminal on the main board is not
connected well with the high pressure switch on the
complete unit.
3. The wiring of the high pressure switch is loosened.
High pressure switch is damaged or poorly contacted.
4. Insufficient or leaking out refrigerant.
5. Check whether LPP input is high level.
1. Abnormal system (e.g.: blockage, etc)
2. Abnormal rotation speed of outdoor motor
(cooling )
3. Abnormal air intake (cooling)
4. System is normal, but the compressor discharge
temperature sensor is abnormal or poorly contacted.
1. The communication line is not connected tightly or
poorly contacted.
Poor contact of any line may cause
malfunction.
2. The match between main board and display panel
is incorrect.
Indoor and outdoor unit boards are
matched incorrectly.
3. Incorrect wire connection.
4. Controller is damaged.
sensor
is
communication