16.

Replacement of control card

NB
Remember to use ESD protection when changing the Control card
1 Remove flat band cables from control card
2 Dismount control card cover (5 screws pos 1, TX 10, torque 1,5 Nm)
3 Mount board stacker (included) into female plug (36 pole)
4 Dismount old control card and replace with new (3 screws TX 10, torque 1,5 Nm)
5 Remount control card cover and flat band cables
1
2
1
2
2
NB
ProfiBus Control card
When install a 12 MB ProfiBus Control card that should run 3 MB, remember to
change parameter 678 to 3 MB. Else the GSD-file in the PLC doesn't work.
NB
Initialising of Control card
When replacing the Control card with a new card, the card initialises it self to the
right motor power. This doesn't happen if using a Control card that have been used.
Release 01/2003
Revise 08/01/2003 by DD Service Manager, Steffen Sundbæk