Siemens SINAMICS G120P CU230P-2 Compact Operating Instructions page 45

Hide thumbs Also See for SINAMICS G120P CU230P-2:
Table of Contents

Advertisement

Control word
Parameter
r2090
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
BACNet
Meaning
.00 p0840 BV20
ON/OFF1
.01 p0844 BV27
No OFF2
.02 p0848 BV28
No quick stop
(OFF3)
.03 p0852 BV26
Enable operation
.04 p1140 BV26
Do not disable
RFG
.05 p1141 BV26
Enable RFG
.06 p1142 BV26
Enable setpoint
.07 p2103 BV22
Acknowledge
faults
.08
---
N/A
Reserved
,
.09
.10 p0854 BV93
Master control by
PLC
.11 p1113 BV21
Direction reversal
.12 ---
N/A
Reserved
.13 p1035 N/A
MOP raise
.14 p1036 N/A
MOP lower
.15 ---
N/A
Reserved
4.3 Connecting the inverter to the fieldbus
Switch on motor
Precondition in order to be able to switch on
the motor (ON command).
The ramp-function generator can be enabled
The output of the ramp-function generator
follows the setpoint
Motor accelerates with the ramp-up time p1120
to the setpoint
Control via fieldbus, the inverter accepts the
process data from the fieldbus
Invert setpoint in the inverter
Increase the setpoint saved in the motorized
potentiometer
Reduce the setpoint saved in the motorized
potentiometer
Commissioning
45