Siemens SINAMICS G120P CU230P-2 Compact Operating Instructions page 36

Hide thumbs Also See for SINAMICS G120P CU230P-2:
Table of Contents

Advertisement

Commissioning
4.2 Commissioning with BOP-2 operator panel
Selecting the suitable control mode
Control mode
Motors that can be
operated
Power Modules
that can be oper-
ated
Application exam-
ples
Closed-loop con-
trol characteristics
Max. output fre-
quency
Torque control
Commissioning
36
U/f control or flux current control (FCC)
Induction motors
Pumps, fans, and compressors with flow
characteristic
Typical correction time after a speed change:
100 ms ... 200 ms
Typical correction
time after a load
surge: 500 ms
The control mode
is suitable to ad-
dress the follow-
ing requirements:
Motor power
ratings
< 45 kW
Ramp-up time 0 → Rated speed (de-
pendent on the rated motor power):
1 s (0.1 kW) ... 10 s (45 kW)
Applications with increasing load torque
without load surges
The control mode is insensitive with respect
to inaccurate motor data settings
550 Hz
Without torque control
Contrary to vector control, no speed control-
ler has to be set
Induction, synchronous and reluctance motors
No restrictions
Pumps and compressors with displacement
machines
Typical correction time after a speed change:
< 100 ms
Typical correction
time after a load
surge: 200 ms
The vector control
controls and limits
the motor torque
Torque accuracy
that can be
achieved: ± 5 % for
15 % ... 100 % of
the rated speed
We recommend vector control for the following
applications:
Motor power ratings > 11 kW
For load surges 10 % ... >100 % of the rat-
ed motor torque
The vector control is necessary for a ramp-up
time 0 → Rated speed (dependent on the rated
motor power):
< 1 s (0.1 kW) ... < 10 s (250 kW).
Torque control with higher-level speed control
Compact Operating Instructions, 01/2016, A5E37058917B AA
Vector control
240 Hz
CU230P-2 Control Units