Installing
3.4 Preassignment of the interfaces
Default setting 18: "2-wire (forward/backward 2)"
DO 0: p0730,
DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 755[0]
Designation in BOP-2: 2-wIrE 2
Default setting 19: "3-wire (enable/forward/backward)"
DO 0: p0730,
DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 755[0]
Designation in BOP-2: 3-wIrE 1
Default setting 20: "3-wire (enable/on/reverse)"
DO 0: p0730,
DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 755[0]
Designation in BOP-2: 3-wIrE 2
20
AO 0: p0771[0], AO 1: p0771[1]
AO 0: p0771[0], AO 1: p0771[1]
AO 0: p0771[0], AO 1: p0771[1]
DI 0: r0722.0, ..., DI 2: r0722.2
DI 0: r0722.0, ..., DI 4: r0722.4
DI 0: r0722.0, ..., DI 4: r0722.4
Compact Operating Instructions, 01/2016, A5E37058917B AA
AI 0: r0755[0]
AI 0: r0755[0]
AI 0: r0755[0]