9. Application and control mode
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
8.2.
8.3.
8.4.
8.5.
8.6.
8.7.
8.8.
8.9.
9.1.
The selection option depends on the Power Module being used. There is no se-
lection option for PM230 Power Modules.
9.2.
4.2 Commissioning with BOP-2 operator panel
If you have selected a motor type > 100, then you must enter the
motor code:
With the correct motor code, the inverter assigns the motor data
the following values.
If you do not know the motor code, then you must set the motor
code = 0, and enter the motor data from p0304 and onwards from
the rating plate.
87 Hz motor operation
The BOP-2 only displays this step if you previously selected IEC
as the motor standard (EUR/USA, P100 = KW 50HZ).
Rated voltage
Rated current
Rated power
Rated frequency
Rated speed
Motor cooling
SELF
Natural cooling
FORCED
Forced-air cooling
LIQUID
Liquid cooling
NO FAN
Without fan
Select the application:
VEC STD
In all applications, which do not fit the other setting
options.
PUMP FAN Applications involving pumps and fans
SLVC 0HZ Applications with short ramp-up and ramp-down
times. However, this setting is not suitable for
hoisting gear and cranes/lifting gear.
PUMP 0HZ Setting only for steady-state operation with slow
speed changes. We recommend setting VEC STD
if load surges in operation cannot be ruled out.
Select the control mode:
VF LIN
U/f control with linear characteristic
VF LIN F
Flux current control (FCC)
VF QUAD
U/f control with square law characteristic
SPD N EN Vector control without encoder
Commissioning
35