Siemens SINAMICS G120P CU230P-2 Compact Operating Instructions page 19

Hide thumbs Also See for SINAMICS G120P CU230P-2:
Table of Contents

Advertisement

Default setting 15: "Process industry"
DO 0: p0730,
DO 1: p0731
Motorized potentiometer, setpoint after the ramp-function generator: r1050
Speed setpoint (main setpoint): p1070[0] = 755[0], p1070[1] = 1050
Designation in BOP-2: Proc
Default setting 17: "2-wire (forward/backward 1)"
DO 0: p0730,
DO 1: p0731
Speed setpoint (main setpoint): p1070[0] = 755[0]
Designation in BOP-2: 2-wIrE 1
CU230P-2 Control Units
Compact Operating Instructions, 01/2016, A5E37058917B AA
AO 0: p0771[0], AO 1: p0771[1]
AO 0: p0771[0], AO 1: p0771[1]
3.4 Preassignment of the interfaces
DI 0: r0722.0, ..., DI 5: r0722.5
DI 0: r0722.0, ..., DI 2: r0722.2
Installing
AI 0: r0755[0]
AI 0: r0755[0]
19