Chapter 2 Installation And Connection Of The System; Requirements Of Installation Environment; Power Supply Requirement - Emerson GIE 4820/3A/3.45KW User Manual

Power supply system
Table of Contents

Advertisement

20

Chapter 2 Installation and Connection of the System

Chapter 2 Installation and Connection of the System
Note:
1)The equipment cannot be transported in the whole-set mode, that is, the rectifier
module and monitoring module should not be installed in the system subrack during
the transportation. Otherwise, the equipment may be damaged.
2)Upon delivery, the rectifier module, monitoring module and system subrack are
all packed up separately for transportation. After unwrapping the package on-site,
please keep the packages for the use next time.

2.1 Requirements of Installation Environment

The environmental conditions listed in Table 2-1 should be considered when
choosing the installation field of the power supply.
Environmental Conditions
Environmental temperature
Humidity
Dust
Sunlight
Corrosive particles
Altitude
Shaking
Insect, nocuousness biology, pest, white ant No
Mildew
Shaking
The main radiation part of the system is rectifier module when the power system is
on operation. There is inner fan inside the rectifier module, a certain room should
be reserved in the front and the back of the module to provide ventilation and heat
radiation. At least 50mm space should be reserved in front of and in back of the
module to ensure the reliable operation of the module.

2.2 Power Supply Requirement

AC mains is preferred for the main power source for AC power supply, and use
single phase three wires. It must assure that protect grounding cable is reliable
Table 2-1 Environmental Conditions for Machine Room
GIE 4820/3A/3.45KW Power Supply System User Manual
Recommended Range
-5~40℃
≤90%RH, no condensation
3
≤1mg/m
No direct irradiation
No contamination, such as salt, acid and smoke,
etc.
≤2000m
2
≤1.5m/s
No
Rain-proof