Mitsubishi Electric CMB-WP-V-GA1 Data Book page 88

Table of Contents

Advertisement

5. Heating [All indoor units]
5-4. Heating capacity with PURY-(E)P200-250YLM-A1 "COP priority mode"
All Indoor units
Model
size
15°C D.B.
(Rated kW)
SHC
15 (1.9)
1.9
20 (2.5)
2.5
25 (3.2)
3.3
32 (4.0)
4.1
40 (5.0)
5.1
50 (6.3)
6.4
* The capacity does not depend on the outdoor temperature.
5-5. Heating capacity with PURY-(E)P300-400YLM-A1 "COP priority mode"
All Indoor units
Model
size
15°C D.B.
(Rated kW)
SHC
15 (1.9)
1.9
20 (2.5)
2.6
25 (3.2)
3.3
32 (4.0)
4.1
40 (5.0)
5.1
50 (6.3)
6.5
* The capacity does not depend on the outdoor temperature.
5-6. Heating capacity with PURY-(E)P450-500YLM-A1 "COP priority mode"
All Indoor units
Model
size
15°C D.B.
(Rated kW)
SHC
15 (1.9)
2.0
20 (2.5)
2.6
25 (3.2)
3.3
32 (4.0)
4.1
40 (5.0)
5.1
50 (6.3)
6.5
* The capacity does not depend on the outdoor temperature.
5-7. Heating capacity with PQRY-P200-500YLM-A
All indoor units
Model
size
15°C D.B.
(Rated kW)
SHC
15 (1.9)
1.9
20 (2.5)
2.5
25 (3.2)
3.2
32 (4.0)
4.0
40 (5.0)
5.0
50 (6.3)
6.3
* The capacity does not depend on the inlet-water temperature.
MEE15K052
SHC: Sensible Heat Capacity (kW)
Indoor air temp.
20°C D.B.
25°C D.B.
SHC
SHC
1.9
1.5
2.5
2.0
3.2
2.6
4.0
3.2
5.0
4.0
6.3
5.0
kcal/h = kW x 860, BTU/h = kW x 3,412
SHC: Sensible Heat Capacity (kW)
Indoor air temp.
20°C D.B.
25°C D.B.
SHC
SHC
1.9
1.4
2.5
1.9
3.2
2.4
4.0
3.0
5.0
3.7
6.3
4.7
kcal/h = kW x 860, BTU/h = kW x 3,412
SHC: Sensible Heat Capacity (kW)
Indoor air temp.
20°C D.B.
25°C D.B.
SHC
SHC
1.9
1.5
2.5
2.0
3.2
2.5
4.0
3.2
5.0
4.0
6.3
5.0
kcal/h = kW x 860, BTU/h = kW x 3,412
SHC: Sensible Heat Capacity (kW)
Indoor air temp.
20°C D.B.
25°C D.B.
SHC
SHC
1.9
1.9
2.5
2.5
3.2
3.2
4.0
4.0
5.0
5.0
6.3
6.3
kcal/h = kW x 860, BTU/h = kW x 3,412
27°C D.B.
SHC
1.3
1.8
2.2
2.8
3.5
4.4
27°C D.B.
SHC
1.2
1.6
2.0
2.6
3.2
4.0
27°C D.B.
SHC
1.3
1.8
2.3
2.8
3.5
4.5
27°C D.B.
SHC
1.6
2.1
2.6
3.3
4.1
5.2