2. CAPACITY TABLES
PURY-
P200YLM-A1
Nominal
25.0
kW
Heating
85,300
Capacity
BTU/h
Input
7.08
kW
PURY-
EP200YLM-A1
Nominal
25.0
kW
Heating
85,300
BTU/h
Capacity
Input
6.92
kW
Outdoor unit temperature correction
To be used to correct outdoor unit only
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
-20
-15
-4
5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-20
-15
-4
5
Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.
MEE15K052
P250YLM-A1
31.5
107,500
10.06
EP250YLM-A1
31.5
107,500
9.84
-10
-5
14
23
Outdoor Temperature
-10
-5
14
23
Outdoor Temperature
Indoor unit temperature correction
To be used to correct indoor unit capacity only
1.1
1.0
0.9
0.8
0.7
0.6
15
16
17
18
19
Indoor Temperature [°CD.B.]
0
5
32
41
0
5
32
41
20
21
22
23
24
25
Indoor Temperature
20°CD.B.
68°FD.B.
10
15
°CW.B.
50
59
°FW.B.
Indoor Temperature
15°CD.B.
59°FD.B.
20°CD.B.
68°FD.B.
25°CD.B.
77°FD.B.
27°CD.B.
81°FD.B.
10
15
°CW.B.
50
59
°FW.B.
26
27
2 - 21