1. SPECIFICATIONS
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
EER
Temp. range of
Indoor
cooling
*3 Outdoor
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor
heating
*3 Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) dB <A>
Sound power level (measured in anechoic room)
Refrigerant
High pressure
piping diameter
Low pressure
FAN
Type x Quantity
Air flow rate
Control, Driving mechanism
Motor output
*4 External static press.
Compressor
Type
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection devices
High pressure protection
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard attachment
Document
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.-5°CD.B. (23°FD.B.)/-6°CW.B. (21°FW.B.) to 21°CD.B. (70°FD.B.)/15.5°CW.B. (60°FW.B.)
with cooling/heating mixed operation.
4.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH
MEE15K052
*1 kW
kcal/h
*1 BTU/h
kW
A
kW/kW
W.B.
D.B.
*2 kW
kcal/h
*2 BTU/h
kW
A
kW/kW
D.B.
W.B.
dB <A>
mm (in.)
mm (in.)
3
m
/min
L/s
cfm
kW
kW
kW
mm
in.
kg (lbs)
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
O, 6.1 mmH
O).
2
2
PURY-EP500YLM-A1 (-BS)
3-phase 4-wire 380-400-415 V 50/60 Hz
56.0
50,000
191,100
21.22
35.8-34.0-32.8
2.63
15.0~24.0°C (59~75°F)
-5.0~46.0°C (23~115°F)
63.0
54,200
215,000
21.67
36.5-34.7-33.4
2.90
15.0~27.0°C (59~81°F)
-20.0~15.5°C (-4~60°F)
50~150% of outdoor unit capacity
WP15~WP50/5~50
63.5
87
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
Propeller fan x 2
380
6,333
13,418
Inverter-control, Direct-driven by motor
0.92 x 2
0 Pa (0 mmH
O)
2
Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
13.4
0.045 (240V)
MEL32
Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
1,710 (1,650 without legs) x 1,750 x 740
67-3/8 (65 without legs) x 68-15/16 x 29-3/16
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
-
-
R410A x 11.8 kg (27 lbs)
HBC controller
349 (770)
Salt-resistant cross fin & aluminium tube
-
Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
WKJ94T758
WKE94G044
Installation Manual
Refrigerant conn. pipe
Main HBC controller: CMB-WP108,1016V-GA1
Sub HBC controller: CMB-WP108,1016V-GB1
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
2 - 13