Mitsubishi Electric CMB-WP-V-GA1 Data Book page 129

Table of Contents

Advertisement

1. SPECIFICATIONS
Model
Number of HBC controller
Power source
Cooling capacity
(Nominal)
Power input
Current input
EER
Temp. range of
Indoor
cooling
Circulating water
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor
heating
Circulating water
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) dB <A>
Sound power level (measured in anechoic room)
Refrigerant
High pressure
piping diameter
Low pressure
Circulating water
Water flow rate
Pressure drop
Operating volume
range
Compressor
Type
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection devices
High pressure protection
Inverter circuit (COMP.)
Compressor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
Water volume in plate
Water pressure Max.
HIC circuit (HIC: Heat Inter-Changer)
Drawing
External
Wiring
Standard attachment
Document
Accessory
Optional parts
Remarks
Notes:
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Water temperature: 30°C (86°F)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.), Water temperature: 20°C (68°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
MEE15K052
Single HBC
*1 kW
kcal/h
*1 BTU/h
kW
A
16.8-16.0-15.4
kW/kW
W.B.
°C
*2 kW
kcal/h
*2 BTU/h
kW
A
14.9-14.2-13.7
kW/kW
D.B.
°C
dB <A>
mm (in.)
mm (in.)
3
m
/h
L/min
cfm
kPa
3
m
/h
kW
kW
mm
in.
kg (lbs)
I
MPa
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the heat source unit needs to be kept below 40°C D.B.
The ambient relative humidity of the heat source unit needs to be kept below 80%.
The heat source unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
PQRY-P350YLM-A
3-phase 4-wire 380-400-415 V 50/60 Hz
40.0
34,400
136,500
9.98
4.00
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
45.0
38,700
153,500
8.87
5.07
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
WP15~WP50/4~35
52
66
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
7.20
120
4.2
44
4.5 ~ 11.6
Inverter scroll hermetic compressor
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
9.5
-
MEL32
Galvanized steel sheets
1,450 x 880 x 550
57-1/8 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
Over-heat protection
R410A x 6.0 kg (14 lbs)
HBC controller
216 (477)
plate type
5.0
2.0
-
WKS94C744
WKE94G131
Installation Manual
Refrigerant conn. pipe
Main HBC controller: CMB-WP108, 1016V-GA1
Sub HBC controller: CMB-WP108, 1016V-GB1
Double HBC
8.72
14.7-13.9-13.4
4.58
8.25
13.9-13.2-12.7
5.45
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
2 - 40