Mitsubishi Electric CMB-WP-V-GA1 Data Book page 81

Table of Contents

Advertisement

1. Power supply for Indoor unit
1-1. Electrical characteristics of Indoor unit
I.ELECTRICAL CHARACTERISTICS
1. Power supply for Indoor unit
PEFY-WP-VMA-E
PEFY-WP20VMA-E
PEFY-WP25VMA-E
PEFY-WP32VMA-E
PEFY-WP40VMA-E
PEFY-WP50VMA-E
PEFY-WP-VMS1-E
PEFY-WP15VMS1-E
PEFY-WP20VMS1-E
PEFY-WP25VMS1-E
PEFY-WP32VMS1-E
PEFY-WP40VMS1-E
PEFY-WP50VMS1-E
PLFY-WP-VBM-E
PLFY-WP32VBM-E
PLFY-WP40VBM-E
PLFY-WP50VBM-E
PFFY-WP-VLRMM-E
PFFY-WP20VLRMM-E
PFFY-WP25VLRMM-E
PFFY-WP32VLRMM-E
PFFY-WP40VLRMM-E
PFFY-WP50VLRMM-E
1-2. Electrical characteristics of HBC controller
HBC controller
CMB-WP108V-GA1
CMB-WP1016V-GA1
CMB-WP108V-GB1
CMB-WP1016V-GB1
MEE15K052
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220-240V / 60Hz
Min.: 198V
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220-240V / 60Hz
Min.: 198V
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220-240V / 60Hz
Min.: 198V
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220-240V / 60Hz
Min.: 198V
Symbols: MCA: Max. Circuit Amps, MFA: Max. Fuse Amps, RLA: Rated Load Amps
Hz
Volts
220
50/60
230
240
220
50/60
230
240
Symbols: MCA: Max.Circuit Amps (=1.25xFLA) FLA: Full Load Amps
IFM: Indoor Fan Motor
MCA(A)
1.18
1.43
1.54
2.47
2.47
MCA(A)
0.63 / 0.63
0.70 / 0.70
0.75 / 0.75
0.83 / 0.82
1.02 / 1.00
1.08 / 1.07
MCA(A)
0.44
0.44
0.57
MCA(A)
0.61
0.69
0.93
0.93
1.28
Power supply
Range+-10%
MCA(A)
Max.: 264V
3.49
Min.: 198V
Max.: 264V
0.06
Min.: 198V
Output: Fan motor rated output
IFM
Output (kW)
FLA(A)
0.085
0.95
0.085
1.14
0.085
1.23
0.121
1.98
0.121
1.98
IFM
Output (kW)
FLA(A)
0.096
0.50 / 0.50
0.096
0.56 / 0.56
0.096
0.60 / 0.60
0.096
0.66 / 0.65
0.096
0.81 / 0.80
0.096
0.86 / 0.85
IFM
Output (kW)
FLA(A)
0.050
0.35
0.050
0.35
0.050
0.45
IFM
Output (kW)
FLA(A)
0.096
0.49
0.096
0.55
0.096
0.74
0.096
0.74
0.096
1.02
RLA(A)
MFA(A)
2.89
15
2.83
2.79
0.05
15
0.05
0.05
1 - 78