2. CAPACITY TABLES

2-1. Correction by temperature

2. CAPACITY TABLES
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity value and
the ratio below, the capacity can be observed at various temperature.
PURY-
P200YLM-A1
Nominal
22.4
kW
Cooling
76,400
BTU/h
Capacity
Input
7.00
kW
PURY-
EP200YLM-A1
Nominal
22.4
kW
Cooling
76,400
BTU/h
Capacity
Input
6.27
kW
Outdoor unit temperature correction
To be used to correct outdoor unit only
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
-5
0
23
32
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
-5
0
23
32
Outdoor unit power input is affected by the indoor and outdoor temperatures as shown in the graph above. Please consult the sales office for details.
MEE15K052
P250YLM-A1
28.0
95,500
9.92
EP250YLM-A1
28.0
95,500
8.77
5
10
15
20
41
50
59
68
Outdoor Temperature
5
10
15
20
41
50
59
68
Outdoor Temperature
Indoor unit temperature correction
To be used to correct indoor unit capacity only
1.2
1.1
1.0
0.9
0.8
15
16
17
18
Indoor Temperature [°CW.B.]
25
30
35
77
86
95
25
30
35
77
86
95
19
20
21
22
23
Indoor Temperature
19°CW.B.
66°FW.B.
40
45
°CD.B.
104
113
°FD.B.
Indoor Temperature
24°CW.B.
75°FW.B.
22°CW.B.
72°FW.B.
20°CW.B.
68°FW.B.
19°CW.B.
66°FW.B.
18°CW.B.
64°FW.B.
16°CW.B.
61°FW.B.
15°CW.B.
59°FW.B.
40
45
°CD.B.
104
113
°FD.B.
24
2 - 14