2. CAPACITY TABLES
2-1-3. How to obtain the equivalent piping length
Refrigerant pipe
1. PQRY-P200YLM-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 × number of bends in the piping) [m]
2. PQRY-P250, 300YLM-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 × number of bends in the piping) [m]
3. PQRY-P350YLM-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 × number of bends in the piping) [m]
4. PQRY-P400, 450, 500YLM-A
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 × number of bends in the piping) [m]
Water pipe
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.55 × number of bends in the piping) [m]
Water piping design
HBC water pipe connection sizes and pipe sizes.
Indoor unit
PEFY-WP-VMS1
PEFY-WP-VMA
PLFY-WP-VBM
PFFY-WP-VLRMM
To outdoor/heat source unit
Note:
*1. Connection of multiple indoor units with one connection (or joint pipe)
• Total capacity of connectable indoor units: Less than 80
• Number of connectable indoor units: Maximum 3 Sets
• Selection of water piping
Select the size according to the total capacity of indoor units to be installed downstream.
• Please group units that operate on 1 branch.
MEE15K052
Connection size
Water inlet
Water outlet
Rc 3/4 screw
Rc 3/4 screw
End connection (brazing)
HBC controller
Water pipework is screw
connections
Indoor
Indoor
Indoor
unit
unit
unit
Pipe size
Water out
Water return
I.D.20mm
I.D.20mm
Twinning pipe (field supply)
Indoor
Indoor
unit
unit
*1
Up to three units for 1 branch hole;
total capacity: below 80
(but in same mode, cooling/heating)
Indoor
unit
2 - 46