Start-up
Initial startup
5.2.4 Heating up for the first time
Boiler with Lambda control
Installation Instructions S3 Turbo | M1081217_en
CAUTION
If the boiler heats up too quickly on initial start-up:
If the output during the heating-up process is too great, the combustion chamber
may be damaged as a result of drying out too rapidly!
For this reason the following applies the first time you heat up the boiler:
❒ Start the firewood boiler for the first time in accordance with the heating
instructions
Heating instructions when starting up a firewood boiler for the first time
❒ Place a piece of wood diagonally across the combustion chamber (see diagram on
left)
➥ Load the boiler with a small amount of firewood (max. 10-20% of the fuel
loading chamber)
➥ Ignite it and allow it to burn slowly with the central pre-heating chamber door
open
NOTICE! Fissures are normal and do not indicate a malfunction
Once the material in the boiler has burnt down, the boiler can be used in accordance
with the operating instructions ("Operating the system" section).
If condensation escapes during the initial heat-up phase, this does not indicate a
fault.
❒ Tip: If this occurs, clean up using a cleaning rag.
❒ Open the insulated door and the fuel loading door
❒ Fill the fuel loading chamber for initial start-up and heat up
NOTICE! See boiler operating instructions