Mitsubishi Electric FR-E720-0.1K Instruction Manual page 33

Fr-e700 series
Hide thumbs Also See for FR-E720-0.1K:
Table of Contents

Advertisement

Start and stop using terminals (External operation)
5.2.2
Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)
POINT
 Switch ON the STF (STR) signal to give a start command.
 Switch ON the RH, RM, or RL signal to give a frequency command.
[Connection diagram]
Forward rotation start
Reverse rotation start
High speed
Middle speed
Low speed
Operation example
Operation at high speed (60Hz)
Screen at power-ON
1.
The monitor display appears.
Start
2.
Turn ON the high-speed switch (RH).
Acceleration  constant speed
Turn ON the start switch (STF or STR). The frequency value on the indication increases in Pr. 7 Acceleration time, and
3.
"
" (60.00Hz) appears.
[RUN] indicator is lit during forward rotation operation and blinks during reverse rotation operation.
 When RM is turned ON, 30Hz is displayed. When RL is turned ON, 10Hz is displayed.
Deceleration
4.
Turn OFF the start switch (STF or STR). The frequency value on the indication decreases in Pr. 8 Deceleration time, and the
motor stops rotating with "
Stop
5.
Turn OFF the high-speed switch (RH)
REMARKS
 Initial values of terminals RH, RM, and RL are 60Hz, 30Hz, and 10Hz. (To change, set Pr. 4, Pr. 5 and Pr. 6.)
 In the initial setting, when two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency
of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
 Maximum of 15-speed operation can be performed. (
29
Inverter
STF
STR
RH
RM
RL
SD
Operation
" (0.00Hz) displayed. [RUN] turns OFF.
Refer to Chapter 4 of the FR-E700 Instruction Manual (Applied).)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
ON
RH
ON
RM
ON
RL