Mitsubishi Electric FR-E720-0.1K Instruction Manual page 15

Fr-e700 series
Hide thumbs Also See for FR-E720-0.1K:
Table of Contents

Advertisement

Wiring
Terminal
Type
Symbol
A, B, C
RUN
FU
Frequency detection
SE
FM
Ethernet connector
Note
 Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage with voltage/current input switch in "I" position (current input is selected) or a current with switch
in "V" position (voltage input is selected) could cause component damage of the inverter or analog circuit of output
devices.
 The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
indicates that terminal functions can be selected using Pr. 178 to Pr. 184 and Pr. 190 to Pr. 192 (I/O terminal function
selection).
 Terminal names and terminal functions are those of the factory set.
 When connecting the DC power supply, be sure to connect the plus side of the power supply to terminal P/+ and
minus side to terminal N/-. Opposite polarity will damage the inverter.
2.3.3
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
Three-phase 200V/400V class
FR-E720-0.1K to 0.75K
N/-
R/L1 S/L2 T/L3
Power supply
11
Terminal Name
1 changeover contact output indicates that the inverter fault occurs.
Relay output
Fault: discontinuity across B-C (continuity across A-C), Normal: continuity across B-C
(fault output)
(discontinuity across A-C) Contact capacity 230VAC 0.3A (power factor = 0.4) 30VDC 0.3A
Switched Low when the inverter output frequency is equal to or
Inverter running
higher than the starting frequency (initial value 0.5Hz).
Switched High during stop or DC injection brake operation.
Switched Low when the inverter output frequency is equal to or
higher than the preset detected frequency and High when less
than the preset detected frequency.
Open collector
Common terminal of terminal RUN and FU.
output common
Used to output a selected monitored item (such as Output
frequency) among several monitored items. (Not output during
For meter
inverter reset.)The output signal is proportional to the
magnitude of the corresponding monitoring item.
Communication can be made via Ethernet.
· Category: 100BASE-TX/10BASE-T
· Data transmission speed: 100Mbps (100BASE-TX) / 10Mbps (10BASE-T)
· Transmission method: Baseband
· Maximum segment length: 100m between the hub and the inverter
· Number of cascade connection stages: Up to 2 (100BASE-TX) / up to 4 (10BASE-T)
· Interface: RJ-45
· Number of interfaces available: 1
· IP version: IPv4
With the PU connector, RS-485 communication can be established.
PU connector
· Conforming standard: EIA-485 (RS-485)
· Communication speed: 4800 to 38400bps · Overall extension: 500m
Use the USB connector to communicate with a personal computer. Setting and monitoring of
the inverter is enabled using FR Configurator2.
USB connector
· Interface: conforms to USB1.1
· Connector: USB mini B connector (receptacle mini B type)
Jumper
P/+
PR
IM
Motor
Description
· Transmission format: Multi-drop link
· Transmission Speed: 12Mbps
FR-E720-1.5K to 3.7K
FR-E740-0.4K to 3.7K
N/- P/+
Jumper
R/L1 S/L2 T/L3
PR
Power supply
Permissible load 24VDC
(Maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal is
on)
 Low
is
when
the
open
collector output transistor is
ON (conducts). High is when
the transistor is OFF (does
not conduct).
Permissible load current 1mA
1440 pulses/s at 60Hz
IM
Motor