(2) Wiring
CAUTION
 Do not install a power factor correction capacitor or surge
suppressor/capacitor type filter on the inverter output side.
These devices on the inverter output side may be
overheated or burn out.
 The connection orientation of the output cables U, V, W to
the motor affects the rotation direction of the motor.
(3) Trial run
CAUTION
 Before starting operation, each parameter must be
confirmed and adjusted. A failure to do so may cause some
machines to make unexpected motions.
(4) Usage
WARNING
 Any person must stay away from the equipment when the
retry function is set as it will restart suddenly after trip.
 Since pressing
key may not stop output depending
on the function setting status, separate circuit and switch
that make an emergency stop (power OFF, mechanical
brake operation for emergency stop, etc.) must be
provided.
 OFF status of the start signal must be confirmed before
resetting the inverter fault. Resetting inverter alarm with
the start signal ON restarts the motor suddenly.
 The inverter must be used for three-phase induction motors.
Connection of any other electrical equipment to the
inverter output may damage the equipment.
 Do not modify the equipment.
 Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the product.
A-2
CAUTION
 The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is
recommended to install both an external thermal and PTC
thermistor for overheat protection.
 Do not use a magnetic contactor on the inverter input for
frequent starting/stopping of the inverter. Otherwise the life
of the inverter decreases.
 The effect of electromagnetic interference must be reduced
by using a noise filter or by other means. Otherwise nearby
electronic equipment may be affected.
 Appropriate measures must be taken to suppress
harmonics. Otherwise power supply harmonics from the
inverter may heat/damage the power factor correction
capacitor and generator.
 When driving a 400V class motor by the inverter, the motor
must be an insulation-enhanced motor or measures must
be taken to suppress surge voltage. Surge voltage
attributable to the wiring constants may occur at the motor
terminals, deteriorating the insulation of the motor.
 When parameter clear or all parameter clear is performed, the
required parameters must be set again before starting
operations because all parameters return to the initial value.
 The inverter can be easily set for high-speed operation.
Before changing its setting, the performances of the motor
and machine must be fully examined.
 Stop status cannot be hold by the inverter's brake function.
In addition to the inverter's brake function, a holding
device must be installed to ensure safety.
 Before running an inverter which had been stored for a long
period, inspection and test operation must be performed.
 Static electricity in your body must be discharged before
you touch the product. Otherwise the product may be
damaged.
 If you are installing the inverter to drive a three-phase
device while you are contracted for lighting and power
service, consult your electric power supplier.
 In order to protect the inverter and the system against
unauthorized access by external systems via network, take
security measures including firewall settings.
 Depending on the network environment, the inverter may
not operate as intended due to delays or disconnection in
communication. Carefully consider the conditions and
safety for the inverter on site.
(5) Emergency stop
CAUTION
 A safety backup such as an emergency brake must be
provided for devices or equipment in a system to prevent
hazardous conditions in case of failure of the inverter or an
external device controlling the inverter.
 When the breaker on the inverter input side trips, the wiring
must be checked for fault (short circuit), and internal parts
of the inverter for a damage, etc. The cause of the trip must
be identified and removed before turning ON the power of
the breaker.
 When any protective function is activated, appropriate
corrective action must be taken, and the inverter must be
reset before resuming operation.
(6) Maintenance, inspection and parts replacement
CAUTION
 Do not carry out a megger (insulation resistance) test on
the control circuit of the inverter. It will cause a failure.
(7) Disposal
CAUTION
 The inverter must be treated as industrial waste.