2 INSTALLATION AND WIRING

AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a molded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
(Refer to page 48)
Molded case circuit breaker (MCCB)
or earth leakage circuit breaker
(ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
inverter at power ON.
(Refer to page 7)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
(Refer to page 7)
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when power
harmonics measures are taken, the power
factor is to be improved or the inverter is
installed near a large power supply system
(500kVA or more). The inverter may be
damaged if you do not use reactors. Select
the reactor according to the model. Remove
the jumpers across terminals P/+ and P1 to
connect the DC reactor.
AC reactor (FR-HAL)
Noise filter (ferrite core) *
(FR-BSF01, FR-BLF)
Install a noise filter (ferrite core)
to reduce the electromagnetic
noise generated from the
inverter. Effective in the range
from about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained. A wire should
be wound four turns or more.
* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.
High power factor
converter (FR-HC2)
Power supply harmonics
can be greatly suppressed.
: Install this as required.
NOTE
 The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low as
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer
to page 8)
 Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit
to protect them from noise. (Refer to page 9)
 Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are
connected, immediately remove them.
 Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install options among the capacitor type
EMC filter FR-BIF (for use in the input side only), the ferrite core type EMC filter FR-BSF01/FR-BLF, Filterpack, and EMC
filter to minimize the interference. (
 Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
Parameter unit
(FR-PU07)
DC reactor (FR-HEL) *
Inverter (FR-E700-NE)
P/+
P1
Noise filter
(capacitor) *
(FR-BIF)
Reduces the
radio noise.
Brake unit
(FR-BU2)
Power regeneration
Resistor unit (FR-BR)
Discharging resistor (GZG, GRZG)
common converter
(FR-CV)
Great braking capability
The regenerative braking capability
is obtained.
of the inverter can be exhibited fully.
Refer to Chapter 3 of the FR-E700 Instruction Manual (Applied)).
Enclosure surface operation panel
(FR-PA07)
By connecting the connection cable
(FR-CB2) to the PU connector, operation
can be performed from FR-PU07, FR-PA07.
P/+
PR
Earth (Ground)
R/L1 S/L2 T/L3
U
V
W
P/+
N/-
Devices connected to the output
Do not install a power factor correction capacitor,
P/+
PR
surge suppressor or capacitor type filter on the output
P/+
side of the inverter. When installing a molded case
PR
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
molded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earthing cable by returning it to the earth
(ground) terminal of the inverter.
USB connector
A personal computer and
an inverter can be connected
with a USB (Ver1. 1) cable.
(
Refer to Chapter 4
of the FR-E700 Instruction
Manual (Applied))
Brake resistor
(FR-ABR, MRS type, MYS type)
Braking capability can be improved. (0.4K
or higher)
Always install a thermal relay when using
a brake resistor whose capacity is 11K or
higher. (Refer to page 19)
Noise filter (ferrite core)
(FR-BSF01, FR-BLF)
Install a noise filter (ferrite core)
to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about
1MHz to 10MHz. A wire should be
wound four turns at a maximum.
Motor
Earth (Ground)
2
6