Operation Processing Upon Instantaneous Power Failure - Mitsubishi A1SJH(S8) User Manual

Hide thumbs Also See for A1SJH(S8):
Table of Contents

Advertisement

4.
CPU MODULE
4.1.3

Operation processing upon instantaneous power failure

The programmable controller CPU detects a momentary power failure when input power
voltage supplied to the power supply module becomes lower than the specified range.
When the programmable controller CPU detects an instantaneous power failure, the
following operation processing is performed.
(1)
(2)
When an instantaneous power failure shorter than allowable momentary power
failure period occurred:
(a) When an instantaneous power failure occurred, the operation processing is
interrupted while the output status is retained.
(b) When the instantaneous power failure is reset, the operation processing will be
continued.
(c) When an instantaneous power failure occurred and the operation was
interrupted, measurement of the watchdog timer (WDT) continues. For instance,
in the case that WDT is 200ms and the scan time is 190ms, if an instantaneous
power failure of 15ms occurs, it causes the watchdog timer error.
Instantaneous power failure occurred
Operation processing upon instantaneous power failure
When an instantaneous power failure longer than the allowable momentary power
failure period occurred:
The programmable controller CPU performs the initial start.
The operation processing is the same as power-on or reset operation with the reset
switch.
Power supply restoration
END 0
4 - 9
END
END
Programmable controller
CPU operation processing

Hide quick links: