Maximum AC
Fuse Protection
Inverter
Fronius Symo 10.0-3-M
Fronius Symo 12.0-3-M
Fronius Symo 12.5-3-M
Fronius Symo 15.0-3-M
Fronius Symo 17.5-3-M
Fronius Symo 20.0-3-M
National Standards
Additional exter-
Depending on the installation, an additional external AC and/or DC disconnect may be re-
nal AC and/or DC
quired if the inverter is installed in a location not easily accessible to utility or fire personnel.
disconnect
Contact your local authorities for additional information.
22
AC ~
max. 80 A
≥ 100 mA
I
ΔN
?
§
NOTE! A residual current circuit breaker for the AC connecting cable may be re-
quired depending on local regulations, the power supply company, and other con-
ditions. A type A residual current circuit breaker with a trip current of at least
100 mA is generally sufficient in this case. However, false alarms can be triggered
for the residual current circuit breaker type A in individual cases and depending
on local conditions. For this reason, Fronius recommends that you use a residual
current circuit breaker suitable for frequency converters.
If excessively long AC or DC cables are laid
in loops in the connection area, fix the cab-
les to the designated eyelets at the top and
bottom of the connection block using cable
ties.
Phases
AC power
3
10,000 W
3
12,000 W
3
12,500 W
3
15,000 W
3
17,500 W
3
20,000 W
RCD
YES
Type A
Maximum fuse protection
C 80 A
C 80 A
C 80 A
C 80 A
C 80 A
C 80 A