Connecting Solar Module Strings To The Inverter (Dc) - Fronius 10.0-3 208-240 Installation Instructions Manual

Inverter for grid-connected photovoltaic systems
Hide thumbs Also See for 10.0-3 208-240:
Table of Contents

Advertisement

Connection Requirements:
1
IMPORTANT Do not use brushes, files or sandpaper. Aluminum particles may get stuck
and can transfer to other cables.
2
3
Repeat the steps above whenever the cable is disconnected and then reconnected.
Connecting Solar
Module Strings to
the Inverter (DC)
IMPORTANT! You should only remove the minimum number of knockouts required for the
available cables.
1
1
NOTE! Take into account local specifications when configuring cable cross sec-
tions.
Carefully clean off the oxide layer of the stripped end of the cable, e.g., using a knife.
After removing the oxide layer of the cable end, rub in a neutral grease, e.g., acid- and
alkali-free Vaseline.
Then immediately connect it to the terminal.
CAUTION! Risk of possible damage to the inverter! Check the polarity and volt-
age of the solar module strings before connection. The voltage must not exceed
the following values:
Symo 10.0-3 – 12.0-3 208–240
-
0–11154 ft (0–3400 m) = 600 V
Symo 10.0-3 – 24.0-3 480
-
0-6561 ft (0-2000 m) = 1000 V
-
6531–8202 ft (2000–2500 m) = 950 V
-
8202–9842 ft (2500-3000 m) = 900 V
-
9842–11,154 ft (3000-3400 m) = 850 V
DC-
DC =
2
2
DC =
2
2
> AWG 10
(6 mm²)
DC+
2.76 in.(70 mm)
1
D1
1
D2
AWG 14 ... AWG 6 copper direct
AWG 6 aluminum direct
AWG 4 copper or aluminum with
input combiner
0.59 in.
(15 mm)
D1
D1
D1
D3
27