Maximum Ac Fuse Protection; Additional External Ac And/Or Dc Disconnect - Fronius Primo 208-240 Operating Instructions Manual

Inverter for grid-connected photovoltaic systems
Hide thumbs Also See for Primo 208-240:
Table of Contents

Advertisement

Maximum AC
AC ~
fuse protection
Fronius 3.8–8.2
Inverter
Fronius Primo 3.8-1 208-240
Fronius Primo 5.0-1 208-240
Fronius Primo 6.0-1 208-240
Fronius Primo 7.6-1 208-240
Fronius Primo 8.2-1 208-240
Fronius Primo 10.0-1 208-240
Fronius Primo 11.4-1 208-240
Fronius Primo 12.5-1 208-240
Fronius Primo 15.0-1 208-240
Additional exter-
Depending on the installation, an additional external AC and/or DC disconnect may be re-
nal AC and/or DC
quired if the inverter is installed in a location not easily accessible to utility or fire personnel.
disconnect
Contact your local authorities for additional information.
2
4
max. 63 A
1
3
Phases
≥ 100 mA
I
ΔN
NOTE! A residual current circuit breaker for the AC connecting cable may be re-
quired depending on local regulations, the power supply company as well as oth-
er conditions. A type A residual current circuit breaker with a trip current of at least
100 mA is generally sufficient in this case. Nevertheless, false alarms can be trig-
gered for the type A residual current circuit breaker in individual cases and de-
pending on local conditions.
For this reason, Fronius recommends that you use a residual current circuit
breaker suitable for a frequency converter.
AC ~
Fronius 10.0–15.0
Max. output
1 / 2
3800 W
1 / 2
5000 W
1 / 2
6000 W
1 / 2
7600 W
1 / 2
8200 W
1 / 2
10,000 W
1 / 2
11,400 W
1 / 2
12,500 W
1 / 2
15,000 W
2
4
max. 100 A
1
3
Max. fuse protec-
tion
63 A
63 A
63 A
63 A
63 A
100 A
100 A
100 A
100 A
19