Part G Specifications; G1. Profinet Interface Specification - YOKOGAWA YFGW410 User Manual

Profinet interface
Hide thumbs Also See for YFGW410:
Table of Contents

Advertisement

Part G Specifications
G1. PROFINET Interface Specification
By selecting "B" (Modbus, OPC, PROFINET) from Communication Protocol, PROFINET in-
terface function becomes available. YFGW410 is certified by PROFIBUS Nutzerorganisation
e.V. (PNO) as the PROFINET IO Device with Conformance Class A and Realtime Class RT_
CLASS_1.
YFGW410 PROFINET interface supports I/O data access from one PROFINET IO controller to
a field wireless device. PROFINET interface also supports PROFIsafe transfer between the SIS
and the safety device. YFGW410 PROFINET interface function can be enabled or disabled by
using FWMC Configurator. When enabled, network size and maximum connection to YFGW410
are reduced as follows:
Network size: 120 devices
Maximum connection of Modbus/TCP: 4 clients
Item
Communication
Interface
Communication
Protocol
PROFINET
Interface
*1
YFGW410 PROFINET interface does not support PROFINET standard redundancy function such as System Redundancy and
Media Redundancy.
*2
When IO Cycle Time is set to 64 millisecond, set "Threshold" to 6 or more. "Threshold" is the number of communication cycles
without valid data after which an error is assumed.
100BASE-TX Port
PROFINET
Maximum number of PROFI-
NET host systems connected
to PROFINET interface
Gateway/Translator function
Maximum number of field wire-
less devices mapped to slots
of PROFINET interface
<G1. PROFINET Interface Specification>
Specification
One of the field network interface ports (F1, F2 and F3
port) is available for PROFINET interface
Node Class
Conformance Class
Communication Class
IO Cycle Time
IO Controller
Translation between ISA100 I/O data and PROFINET
I/O data
Transfer PROFIsafe safety PDU between PROFIsafe-
enabled GasSecure GS01 field wireless device and
PROFIsafe controller
Process value or PROFIsafe
safety PDU
Process value and PROFIsafe
safety PDU
G1-1
IO Device
CC-A *
1
RT_CLASS_1
64, 128, 256, 512
milliseconds *
2
1
120
60
IM 01W02D01-21EN