Representation Of Analog Values In The Current Measuring Ranges - Siemens SIMATIC S7-1500 Manual

Analog input module ai 8xu/i/rtd/tc st
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Table C- 6
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-4864
-32768
C.3

Representation of analog values in the current measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table C- 7
Values
dec
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
C.3 Representation of analog values in the current measuring ranges
Voltage measuring range 1 to 5 V
Voltage measuring range
hex
1 to 5 V
7FFF
>5.704 V
7EFF
5.704 V
6C01
6C00
5 V
5100
4 V
1
1 V + 144.7 µV
0
1 V
FFFF
ED00
0.296 V
8000
< 0.296 V
Current measuring range ±20 mA
Current measuring range
hex
±20 mA
7FFF
>23.52 mA
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
8000
< -23.52 mA
Representation of analog values
Range
Overflow
Overshoot range
Rated range
Undershoot
range
Underflow
Overflow
Overshoot range
Rated range
Undershoot
range
Underflow
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp