Structure of data record 192 for dynamic reference temperature
The following figure shows an example of the structure of data record 192 for channel 0. The
structure for data records 193 to 199 is identical.
Figure B-4
Valid values for fixed temperature compensation
You can enter the selectable values at byte 1 of the data record for the corresponding
channel. The selectable values must lie within the permitted value range, see following table.
The resolution is a tenth of a degree.
Table B- 14
Temperature unit
Celsius (default)
Fahrenheit (default)
Kelvin (default)
Celsius (climatic)
Fahrenheit (climatic)
Kelvin (climatic)
Additional information
For more information on compensation of the reference junction temperature via data record
refer to the Analog value processing
(http://support.automation.siemens.com/WW/view/en/67989094) function manual in the
internet.
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
B.2 Structure of a data record for dynamic reference temperature
Structure of data record 192
Valid values for temperature compensation via data record
Decimal
-1450 to 1550
-2290 to 3110
1282 to 3276
-14500 to 15500
-22900 to 31100
12820 to 32760
Parameter data records
Hexadecimal
FA56
to 60E
H
H
F70E
to C26
H
H
502
to CCC
H
H
C75C
to 3C8C
H
H
A68C
to 797C
H
H
3214
to 7FF8
H
H
63