Smoothing
The individual measured values are smoothed using filtering. The smoothing can be set in 4
levels.
Smoothing time = number of module cycles (k) x cycle time of the module.
The following figure shows the number of module cycles after which the smoothed analog
value is almost 100%, depending on the set smoothing. It is valid for each signal change at
the analog input.
①
②
③
④
Figure 4-3
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Manual, 09/2016, A5E03484864-AD
None (k = 1)
Weak (k = 4)
Medium (k = 16)
Strong (k = 32)
Smoothing with AI 8xU/I/RTD/TC ST