Parameter data records
B.1 Parameter assignment and structure of the parameter data records
Valid values for fixed reference temperatures
The values that you can set for fixed reference temperatures must be in the valid range of
values. The resolution is a tenth of a degree.
Table B- 6
Temperature unit
Celsius (default)
Fahrenheit (default)
Kelvin (default)
Hardware interrupt limits
The values that you can set for hardware interrupts (high/low limit) must not violate the
over/underrange of the respective rated measuring range.
The following tables list the valid hardware interrupt limits. The limits depend on the selected
measurement type and measuring range.
Table B- 7
Voltage
±50 mV, ±80 mV, ±250 mV, ±500 mV,
±1 V, ±2.5 V, ±5 V, ±10 V
32510
-32511
Table B- 8
Current
±20 mA
32510
-32511
Table B- 9
Thermocouple
°C
20699
60
Valid values for fixed reference temperatures
Voltage limits
Current and resistance limits
4 mA to 20 mA /
0 mA to 20 mA
32510
-4863
Limits for thermocouple types B, C, E, and J
Type B
°F
K
32765
23431
1
321
2733
Decimal
-1450 to 1550
-2290 to 3110
1282 to 3276
1 V to 5 V
32510
-4863
Resistor
(all configurable measuring ranges)
32510
1
Type E
°C
°F
K
11999
21919
14731
-2699
-4539
33
Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0)
Hexadecimal
FA56
to 60E
H
H
F70E
to CCC
H
H
502
to 10BA
H
H
High limit
Low limit
High limit
Low limit
Type J
°C
°F
K
14499
26419
17231
-2099
-3459
633
Manual, 09/2016, A5E03484864-AD
High limit
Low limit