Technical Data; General Unit Data; Environmental Conditions - Siemens LME11 series Manual

Gas burner controls
Table of Contents

Advertisement

Technical data

General unit data

Environmental
conditions
Building Technologies
HVAC Products
Mains voltage
Mains frequency
Power consumption
External primary fuse (Si)
Mounting position
Input current at terminal 12
Weight
Safety class
Degree of protection
Perm. cable length terminal 1
Perm. cable length from QRA... to
AGQ3...A27 (lay separate cable)
Remote reset laid separately
Perm. cable length terminals 8 and 10
Perm. cable lengths other terminals
Current rating
- Terminal 3
- Terminals 4, 5, 7 and 9 (11) Max. 1.7 A
- Terminal 10
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Condensation, formation of ice and ingress of water are not permitted!
AC 120 V +10 % / -15 %
AC 230 V +10 % / -15 %
50...60 Hz ±6 %
12 VA
max. 10 A (slow)
optional
max. 5 A
approx. 160 g
I
IP 40 (to be ensured through mounting)
max. 1 m at a line capacitance of 100 pF/m
(max. 3 m at 15 pF / m)
max. 20 m at 100 pF / m
max. 20 m at 100 pF / m
max. 20 m at 100 pF / m
max. 3 m at 100 pF / m
At cosϕ ≥ 0.6
Max. 2.7 A
(15 A for max. 0.5 s → only LME2...)
Max. 1 A
DIN EN 60721-3-1
class 1K3
class 1M2
-20...+60 °C
< 95 % r.h.
DIN EN 60 721-3-2
class 2K2
class 2M2
-20...+60 °C
< 95 % r.h.
DIN EN 60 721-3-3
class 3K3
class 3M3
-20...+60 °C
< 95 % r.h.
At cosϕ = 1
Max. 3 A
Max. 2 A
Max. 1 A
9/23
CC1N7101en
29.06.2006

Advertisement