(S) means the parameter is effective, when Modbus Type of GW-7553-B /
GW-7553-M is Slave.
(T) means the parameter is effective, when Modbus Format of GW-7553-B /
GW-7553-M is TCP.

4.4 The Configuration of the modules

The user can set the number and size of the I/O modules in the PROFIBUS
configuration tool. The settings of the modules are described below.
Max. I/O modules:32 modules
System setting module:3 byte output , 6byte input
Output module:Output Relay/Coil => 1~32 Bytes
Input module:Input Relay/Coil => 1~32 Bytes
Max. length of I/O data:480 Bytes
Output length:0~240 Bytes
Input length:0~240 Bytes
Note:
The user must add "System setting module" at the first module before the other
modules, else the GW-7553-B / GW-7553-M will send the diagnostic messages
to PROFIBUS Master and the system will be abnormal.
The modules have module parameters about the communication settings. The
module parameters are shown in the below:
A. Output Relay/Coil module parameters:
Modbus Slave Device ID(M):0~247
Start Address(M):0~65535
NO. of Relay/Coil(M):8*(n-1)+1 ~ 8*n Bits
n=Module size/Byte
TCP_Connect_Index(T)(M):1~8
B. Output Register module parameters:
Modbus Slave Device ID (M):0~247
Start Address(M):0~65535
Change Word Order:Enable/Disable (Even module only)
TCP_Connect_Index(T)(M):1~8
GW-7553-B / GW-7553-M PROFIBUS/Modbus TCP Gateway User Manual (Version 1.35, May/2017)
PAGE: 38
Output Register
Input Register
=> 1~64 Words
=> 1~64 Words