Environmental Type Tests - Siemens RUGGEDCOM RS900W Installation Manual

Wireless ethernet switches
Table of Contents

Advertisement

RUGGEDCOM RS900W
Installation Guide
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RS900W meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
ESD
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Dielectric Strength

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
EMC and Environmental Type Tests
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Description
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
Vibration
Shock
2.5 kV Common and Differential Mode @ 1 MHz
2.5 kV Common and Differential Mode @ 1 MHz
Test Levels
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Db
95% (Non-Condensing),
55 °C (131 °F), 6 Cycles
2 g @ 10-150 Hz
30 g @ 11 ms
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV Common Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
1.5 kV
2 kV
Severity Levels
Class 2
Class 2
Chapter 6
Certification
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents