Mounting the RMD (if equipped)
Step 3: Wire the Ground Terminal
Step 4: Wire the Digital Outputs (if equipped)
The Remote Modular Display (RMD) is a product option for 9200 TRAN
meters. The RMD can be mounted in either a standard DIN or ANSI cutout.
9200 RMD Retrofit Instructions
See the
Remote Modular Display Connections
Connector Type
Wire
N
OTE
Only use the supplied cable to connect the RMD.
Wire the meter's ground terminal
2
14 AWG (2.1mm
) or larger wire.
Connect the power supply G (ground) terminal to the same point as the meter
terminal.
C
AUTION
Do not use metal door hinges as a ground path.
Two optional Form A digital relays can be used for energy pulsing and/or
control applications.
Digital Output Connections
Connector Type
Wire
Maximum Forward Current
Maximum Voltage
Maximum Current
Isolation
for more information.
RJ11
26 gauge 6 conductor cable
to the switchgear earth ground using a
Captured wire
24 AWG to 18 AWG wire
2
(0.08 mm
to 0.82 mm
150 mA
200 VDC/VAC
150 mA
Optical
2
)