Installation Considerations

Installation and maintenance of the 9200 meter should only be performed by qualified, competent personnel
that have appropriate training and experience with high voltage and current devices. The meter must be
installed in accordance with all Local and National Electrical Codes.
D
ANGER
Failure to observe the following instructions may result in severe injury or death.
During normal operation of the
throughout the connected potential transformer (PT), current transformer (CT), digital (status) input, control
power and external I/O circuits. PT and CT secondary circuits are capable of generating lethal voltages
and currents with their primary circuit energized. Follow standard safety precautions while performing any
installation or service work (i.e. removing PT fuses, shorting CT secondaries, etc).
The terminal strips on the meter base should not be user-accessible after installation.
Do not use digital output devices for primary protection functions. These include applications where the
devices perform energy limiting functions or provide protection of people from injury. Do not use the
in situations where failure of the devices can cause injury or death, or cause sufficient energy to be
released that can start a fire. The meter can be used for secondary protection functions.
Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or communications terminals. Refer
to the label on the
9200
C
AUTION
Observe the following instructions, or permanent damage to the meter may occur.
The
meter offers a range of hardware options that affect input ratings. The
9200
number label lists all equipped options. Applying current levels incompatible with the current inputs will
permanently damage the meter. This document provides installation instructions applicable to each hard-
ware option.
The 9200 meter's chassis ground must be properly connected to the switchgear earth ground for the
noise and surge protection circuitry to function correctly. Failure to do so will void the warranty.
Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws: 1.35 Nm (1.00 ft-lbf)
max. Captured-wire type (digital inputs/outputs, communications, power supply: 0.90 Nm (0.66 ft.lbf)
max.
FCC Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense. The Ringer Equivalence Number (REN) for the 9200 optional internal
modem is 0.6. Connection to the 9200 internal modem should be made via an FCC Part 68 compliant
telephone cord (not supplied). The 9200 cannot be used on a public coin phone service or party line services.
Network Compatibility Notice for the Internal Modem
The internal modem in meters equipped with this option is compatible with the telephone systems of most
countries in the world, with the exception of Australia and New Zealand. Use in some countries may require
modification of the internal modem's initialization strings. If problems using the modem on your phone system
occur, please contact Siemens Customer Service

Standards Compliance

4
meter, hazardous voltages are present on its terminal strips, and
9200
meter for the maximum voltage level the device can withstand.
CSA: Certified to CAN/
CSA C22.2 No.1010-1
Certified to
CE: approved
UL 3111
9200
meter's serial
9200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents