8-4. Check Codes Displayed on Remote Control and SMMS-e Outdoor Unit
(7-Segment Display on I/F Board) and Locations to Be Checked
For other types of outdoor units, refer to their own service manuals.
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
control
code
E01
E02
E03
E04
No. of indoor units from
which signal is received
normally
E06
E06
E07
Duplicated indoor
address
E08
E08
E09
E10
01:
Indoor-outdoor
communication
02:
E12
E12
Outdoor-outdoor
communication
E15
E15
Location
of
Description
System status
detection
Remote
Indoor-remote
Stop of
control
control
corresponding
communication
unit
trouble
(detected at
remote
control end)
Remote
Remote control
Stop of
control
transmission
corresponding
trouble
unit
Indoor
Indoor-remote
Stop of
unit
control
corresponding
communication
unit
trouble
(detected at
indoor end)
Indoor
Indoor-outdoor
Stop of
unit
communication
corresponding
circuit trouble
unit
(detected at
indoor end)
I/F
Signal lack of
All stop
indoor unit
I/F
Indoor-outdoor
All stop
communication
circuit trouble
(detected at
outdoor end)
Indoor
Duplicated
All stop
unit I/F
indoor address
Remote
Duplicated
Stop of
control
master remote
corresponding
control
unit
Indoor
Indoor inter-
Stop of
unit
MCU
corresponding
communication
unit
trouble
I/F
Automatic
All stop
address starting
trouble
I/F
Indoor unit not
All stop
found during
automatic
address setting
Trouble detection
condition(s)
Communication between indoor
P.C. board and remote control is
disrupted.
Signal cannot be transmitted from
remote control to indoor unit.
There is no communication from
remote control (including wireless)
or network adaptor.
Indoor unit is not receiving signal
from outdoor unit.
Indoor unit initially
communicating normally fails
to return signal for specified
length of time.
Signal cannot be transmitted from
outdoor to indoor units for 30
seconds continuously.
More than one indoor unit are
assigned same address.
In two remote control configuration
(including wireless), both controls
are set up as master. (Header
indoor unit is shut down with alarm,
while follower indoor units continue
operating.)
Communication cannot be
established/maintained upon
turning on of power or during
communication.
• Indoor automatic address setting
is started while automatic address
setting for equipment in other
refrigerant line is in progress.
• Outdoor automatic address
setting is started while automatic
address setting for indoor units is
in progress.
Indoor unit cannot be
detected after indoor
automatic address setting is
started.
88
Check items (locations)
• Check remote control inter-unit
tie cable (A/B).
• Check for broken wire or
connector bad contact.
• Check indoor power supply.
• Check for defect in indoor P.C.
board.
• Check remote control address
settings (when two remote
controls are in use).
• Check remote control P.C. board.
• Check internal transmission
circuit of remote control.
--- Replace remote control as
necessary.
• Check remote control and
network adaptor wiring.
• Check order in which power was
turned on for indoor and outdoor
units.
• Check indoor address setting.
• Check indoor-outdoor tie cable.
• Check outdoor terminator resistor
setting (SW30, Bit 2).
• Check power supply to indoor unit.
(Is power turned on?)
• Check connection of indoor-
outdoor communication cable.
• Check connection of
communication connectors on
indoor P.C. board.
• Check connection of
communication connectors on
outdoor P.C. board.
• Check for defect in indoor P.C.
board.
• Check for defect in outdoor P.C.
board (I/F).
• Check outdoor terminator resistor
setting (SW30, Bit 2).
• Check connection of indoor-
outdoor communication circuit.
• Check indoor addresses.
• Check for any change made to
remote control connection
(group/individual) since indoor
address setting.
• Check remote control settings.
• Check remote control P.C.
boards.
• Check for defect in indoor P.C.
board
• Perform automatic address
setting again after disconnecting
communication cable to that
refrigerant line.
• Check connection of indoor-
outdoor communication line.
• Check for trouble in indoor power
supply system.
• Check for noise from other devices.
• Check for power failure.
• Check for defect in indoor P.C.
board.