Control Outline - Toshiba MMU-AP0072H2UL-1 Service Manual

Hide thumbs Also See for MMU-AP0072H2UL-1:
Table of Contents

Advertisement

6-1. 4-Way Cassette Type, Compact 4-Way Type, Ceiling Type
No.
Item
1
When power
supply is reset
2
Operation
mode selection
3
Room temp.
control

6. CONTROL OUTLINE

Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are
distinguished and the control is selected according to the
distinguished result.
2) Setting of indoor fan speed and existence of air direction
adjustment
Based on EEPROM data, select setting of the indoor fan
speed and the existence of air direction adjustment.
3) If resetting the power supply during occurrence of a
trouble, the check code is once cleared. After ON/OFF
button of the remote control was pushed and the operation
was resumed, if the abnormal status continues, the check
code is again displayed on the remote control.
1) Based on the operation mode selecting command from the
remote control, the operation mode is selected.
Remote control
command
STOP
FAN
COOL
DRY
HEAT
1) Adjustment range: Remote control setup temperature (°F [°C] )
Wired type
64°F [18°C] to 84°F [29°C]
Wireless type
63°F [17°C] to 86°F [30°C]
2) Using the Item code 06, the setup temperature in heating
operation can be corrected.
Setup data
Setup temp.
+0°F
Correction
[+0°C]
Setting at shipment
Setup data
2
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
COOL/DRY
0
2
4
+3.6°F
+7.2°F
[+2°C]
[+4°C]
30
Remarks
Air speed (rpm)/
Air direction adjustment
HEAT
64°F [18°C] to 84°F [29°C]
63°F [17°C] to 86°F [30°C]
Shift of suction
temperature in heating
operation
6
+10.8°F
Except while sensor of
[+6°C]
the remote control is
controlled
(Code No. [32], "0001")

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents