Input Configuration Options - NAPCO StarLink SLE Installation Instructions Manual

Residential/commercial series
Table of Contents

Advertisement

Application
FACP with DACT
Use IN2 or IN3 only for trouble.
1
Panel reports via dialer capture,
but Linecut reports via an input
on radio.
FACP with DACT
Use IN1 (not supervised) either
2
for trouble or alarm. Panel has
trouble (or alarm) relay that
closes on the condition.
FACP without DACT
Use IN2 or IN3 for both Alarm
3
and Trouble on one input.
Panel has alarm and trouble
relay outputs.
BURG with DACT
Use IN2 or IN3 for only trouble
4
reporting. Panel reports via
dialer capture but Linecut re-
ports via an input on radio.
BURG without DACT
Use IN2 or IN3 for both Alarm
and Trouble. Panel has alarm
and Trouble Relay/PGM out-
5
puts. Two EOLRs are needed
since for UL Burg it is required
to detect both wire breaks and
shorts.
BURG without DACT: Armed
Status
Use IN2 or IN3 for Armed Sta-
6
tus input. Two EOLRs are
needed since for UL Burg it's
required to supervise for both
wire breaks and shorts.
*Note: On line cut, PGM1 will activate.
20

Input Configuration Options

Armed
Cut
Open
Short
Wire*
TBL
TBL
TBL
TBL
-
(or
-
ALARM)
TBL
TBL
ALARM
ALARM
ALARM
ALARM
ALARM
TBL
ALARM
TAMPER
N/A
ALARM
ALARM
Disarmed
Resend
TBL every
Cut
Open Short
24 Hrs.
Wire*
-
-
-
Yes
-
-
-
Yes
-
-
-
Yes
TBL
TBL
TBL
TBL
TBL
TBL
TBL
N/A
TBL
StarLink
SLE Commercial Series Alarm Communicators -- Installation Instructions
NOC Inputs
"Function"
Selection
Supervised Fire
Requires two EOLRs. Radio
Trouble (Linecut)
Un-Supervised
Fire Trouble (use
Non-supervised (use conduit
'User Defined'
selection for
Alarms)
Requires two EOLRs. The
Trouble relay N.C. contact
Supervised Fire
(energized opens) is put in
Alarm/Trouble
series with one ELOR. Alarm
relay put across both EOLR
Requires two EOLRs. Pro-
gram panel to report Open/
Supervised Burg-
Close (radio remembers last
No
Linecut
state of panel for Napco panels
when used with local download
Requires two 10K EOLRs.
Three off normal conditions
can be detected, namely, cut
wire, shorted loop and one of
the EOLR's having a closed
contact in series. The Trouble
relay N.C. contact (energized
opens) is put in series with one
Supervised Burg
ELOR. The Alarm relay N.O.
No
Alarm/Trouble
EOLRs and trouble relay. The
panel Armed or Disarmed state
is determined by a separate
input (see Option 6 in this table
below for armed status opera-
tion). (Note: The Alarm relay
should NOT activate on 24hr
Requires two 10K EOLRs. A
relay or PGM for Arm/Disarm
status goes in series with one
EOLR where open is disarmed
Supervised Arm/
No
and closed is armed. The other
Disarm Status
EOLR is across the series
combination (relay for Arm/
Disarm and first ELOR) to
provide the loop supervision.
Comments
reports in CID.
activation requires +12V)
and trouble relay.
cable).
contact is put across both
zones.)