Charging refrigerant

f The R-410A refrigerant is blended refrigerant. Add only liquid refrigerant.
f Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the refrigerant
using a scale.
Important information regulation regarding the refrigerant used
This product contains uorinated greenhouse gases. Do not vent gases into the atmosphere.
• Inform user if system contains 5 tCO
CAUTION
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered
by quali ed personnel only. In case situation above (5 tCO
which has responsibility for nal check) has to provide a maintenance book, with all the information recorded
according to REGULATION (EU) No 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April
2014 on uorinated greenhouse gases.
Please ll in the following indelible ink on the refrigerant charge label supplied
with this product on and on this manual.
f ① The factory refrigerant charge of the product.
f ② The additional refrigerant amount charged in the eld.
f ①+② The total refrigerant charge.
a. Factory refrigerant charge of the product: See unit name
plate.
NOTE
b. Additional refrigerant amount charged in the eld.
(Refer to the above information for the quantity of
refrigerant replenishment.)
c. Total refrigerant charge.
d. Refrigerant cylinder and manifold for charging.
f Before charging, check whether the refrigerant cylinder has a siphon attached or not and position the cylinder
accordingly.
Charging using a cylinder with a
siphon attached
Charge the liquid refrigerant with
the cylinder in upright position.
e or more of uorinated greenhouse gases. In this case, it has to be checked
2
e or more of R-410A), installer (or recognized person
2
Charging using a cylinder
without a siphon attached
Charge the liquid refrigerant with
the cylinder in up-side-down
position.
ENGLISH-33
Indoor unit
d
Outdoor unit
Unit
kg
①, a
②, b
① + ②, c
Refrigerant type
GWP value
R-410A
❋ GWP=Global Warming Potential
❋ Calculating tCO
e : kg x GWP / 1000
2
tCO
e
2
2088