Charging refrigerant

f Measure the quantity of the refrigerant according to the length of the liquid side pipe . Add quantity of the refrigerant
f
using a scale .
Important information: regulation regarding the refrigerant used
This product contains fluorinated greenhouse gases . Do not vent gases into the atmosphere .
• Inform user if the system contains 5 tCO2e or more of fluorinated greenhouse gases . In this case, it must be
checked for leakage at least once every 12 months, according to regulation No . 517/2014 . This activity must be
CAUTION
covered by qualified personnel only . In the case of the situation above, the installer (or authorized person with
responsibility for final check) must provide a maintenance book, with all the information recorded, according
to REGULATION (EU) No . 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on
fluorinated greenhouse gases .
Please fill in the following with indelible ink on the refrigerant charge label supplied with this product and on this
manual.
f ① the factory refrigerant charge of the product .
f
f ② the additional refrigerant amount charged in the field .
f
Indoor unit
a Factory refrigerant charge of the product: see unit name plate .
b Additional refrigerant amount charged in the field . (Refer to the above information for the quantity of
NOTE
refrigerant replenishment . )
• The filled-out label must be adhered in the proximity of the product charging port .
(ex . onto the inside of the stop valve cover . )
CAUTION
R-32
GWP = 675
Outdoor
unit
ENGLISH-45
Unit
kg
, a
, b
DO NOT CHARGE
Refrigerant type
R-32
• GWP: Global Warming Potential
• Calculating tCO2e: kg x GWP/1000