Connecting the cable

Power cable specifications
1 phase
Outdoor unit
AE090JXEDEH
AE120JXEDEH
AE140JXEDEH
AE160JXEDEH
f The power cable is not supplied with Air to Water Heat pump.
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f This Equipment complies with IEC 61000-3-12.
3 Phase
Outdoor unit
AE090JXEDGH
AE120JXEDGH
AE140JXEDGH
AE160JXEDGH
f The power cable is not supplied with Air to Water Heat pump.
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
f This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].
Rated
Hz
Volts
Min
50
220-240
198
50
220-240
198
50
220-240
198
50
220-240
198
Rated
Hz
Volts
Min
50
380-415
342
50
380-415
342
50
380-415
342
50
380-415
342
ENGLISH-17
Voltage Range
Max
Min. Circuit Amps.
264
264
264
264
Voltage Range
Max
Min. Circuit Amps.
457
457
457
457
MCA
MFA
Max. Fuse Amps.
22 A
27.5 A
28 A
35 A
30 A
37.5 A
32 A
40 A
MCA
MFA
Max. Fuse Amps.
10 A
16.1 A
10 A
16.1 A
11 A
16.1 A
12 A
16.1 A