Figure 20 Feeder control function (Phase low, Overfeed timer)
1 Deadband
2 Setpoint
3 Overfeed timer
4 Time (x-axis)
• Event Control Function (refer to
Option
Description
Set setpoint
Sets the value where the relay will turn on.
Deadband
Sets a hysteresis so the relay will not swing unregulated when the process value converges
to the setpoint.
OnMax timer Sets the maximum time the relay can stay on independent from the measured value (default:
+ 0 min).
OffMax timer Sets the maximum time the relay can stay off independent from the measured value (default:
+ 0 min).
OnMin timer
Sets the minimum time the relay can stay on independent from the measured value (default: +
0 min).
OffMin timer
Sets the minimum time the relay can stay off independent from the measured value (default: +
0 min).
34 English
5 ON delay
6 OFF delay
7 Source (y-axis)
Figure
21,
Figure 22
and
Figure
23)