Zone Monitor Unit CZMU352
Installation
1.
Separate the two halves of the unit.
2.
Drill out (or knock out) the required cable entries in the surface mounting back-
box.
3.
Fit the back-box in position and pass the wires into it.
4.
Connect the unit according to the diagram below.
Notes:
No addressing of the interface is required. See control panel operation for details.
Standard Connections
Analogue Addressable Loop
-
E
OUT
Notes:
1.
This unit can only be used with CDBB300 detector base and compatible detectors.
2.
Only connect cable screen to its adjacent earth terminal.
3.
The end of line resistor must always be fitted, even if the spur is unused.
4.
Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage.
5.
Maximum number of call points allowed is unlimited.
6.
Detector zone end of line device is EOLM-1 (supplied)
7
Callpoint zone has end of line resistor
-
+
E
+
IN
LOOP
Callpoints can be
connected with detectors
on detector zone if
preferred
12K
- OUT +
- IN
+
- OUT +
- IN
+
-
-
E
+
E
CALL
DETECTOR ZONE
POINT
ZONE
76
EOLM-1
+