System Wiring ( Optional Board)
This boards is used to extend the flexibility of the CF2000 by splitting each loop into four
circuits .One circuit will allow the use of 99 addressable devices wired in a loop. The second
circuit can accommodate up to 32 addressable Call point in a spur configuration. Up to 32
conventional call point can be wired in the third circuit where the line is monitored using End of
Line Resistor and finally the forth circuit has a maximum capacity of up to 20 Conventional
detectors again the line is monitored with an active end of line device EOLM-1.
Upto 99 Analogue Addressable Devices
Upto 99 Analogue Addressable Devices
32
Upto 32 Analogue
Addressable Callpoints
EOLM-1
Upto 20 Coventional
Detectors
Upto 32 Coventional
Callpoints
Upto 32 Analogue
Addressable Callpoints
EOLM
Upto 20 Coventional
Detectors
Upto 32 Coventional
Callpoints