Technical Specification - Cooper CF2000 Installation Manual

Table of Contents

Advertisement

Technical Specification

Power Supply (Approved EN54 pt 4)
Mains
Nominal Voltage
Nominal Current
Maximum Current
Input Fuse R1
Output Voltage including tolerances
Ripple Voltages
Maximum Loadings
Standby Current (2 Loops Loaded)
* I max a, I max b & I min = Current as specified in BSEN54-4 Published 2006 (Amendments 1 & 2)
Batteries
Number of Batteries
Manufacturer:
Capacity
Battery Fuse
Maximum battery current;
Standby current (mA)
Maximum Charging Current to the Batteries
Float Voltage
Final Voltage
Charging Characteristics
Maximum current drawn from the batteries
when the mains is not available
Deep Discharge Protection
Battery Internal Impedance Fault
Inputs
Addressable Loops
Max Number
Max Loop Load per loop
Max Number of Addressable Devices per loop
Class Change
contact
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE
DISPOSE OF THE USED BATTERIES ACCORDING TO THE INSTRUCTIONS
: 230 Vac + 10%, -15%
: 40mA
: 500mA
: Anti Surge 1.6Amp
: 26V
: 26V RAW
: 5Volt Output
: 26V
: 26V RAW
: 5Volt Output
: 26V O/P
: 26V RAW O/P
: 5V
: 26V
: 26V RAW
: 26V
: 26V RAW
: 5V
: 2
:YUASA NP7-12
: 7 Ah
: 6.3A Anti-Surge (F4)
: 3.0 Amps
: 125 (2 loops)
: 0.65Amp
: 27.4 Volts
: 21.0Volts
: Constant Voltage with 0.65A
limit with temperature compensation
: 3.0Amps
: 20.6 Volts
: >0.5 ohms
: 2
: 200 ma
: 200
: Operated by external volt free
CAUTION
(Appendix page 113)
24
= 18.5 to 29.5Volts
= 18.5 to 29.5Volts
= 4.6V to 5.5V
= 800mV
= 800mV
= 430mV
}
= 0.48A
* I max b
= 1.2A
= 0.5A
}
= 140mA
* I max a
= 50mA
}
= 140mA
* I min
= 50mA
= 30mA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents