Cooper CF2000 Installation Manual page 12

Table of Contents

Advertisement

Compatible Equipment
The range of compatible sensors for the CF2000 system consists of the following:
Model
Operating voltage
Standby current (max)
Alarm current (max)
Ambient Temperature (max)
Ambient Temperature (min)
Alarm temperature (static)
Heat sensor class
as defined by EN54-5:2000
Radioactive material/strength
Relative humidity (non cond)
Height (w/o base)
Height (with base)
Diameter
Weight (w/o base)
Material
Colour
CAP320 Analogue Photoelectric Sensor, this is the most
commonly used sensors and is most suitable for detecting
slow burning fires.
The status LED can be programmed to either be
permanently off under normal conditions or to pulse in
order to confirm that it is in communication with the
CF2000 control panel.
CAPT340 Analogue Photo/thermal Sensor, this is a new
addition to the Cooper Fire Systems range of sensors. It is
the ideal sensor for a multi-use environment as it has an
excellent response to smouldering and fast burning fires.
Photo/thermal sensors can be programmed for thermal
only operation at certain times of day
The status LED can be programmed to either be
permanently off under normal conditions or to pulse in
order to confirm that it is in communication with the
CF2000 control panel.
CAI310
CAP320
CAH330
18 TO 30V dc
220µA
5mA
A1R
60ºC
BS
CS
-20ºC
A1R
N/A
BS
CS
A1R, BS, CS
N/A
control panel
selectable
Am 18.5KBq
0 to 95%
34mm
47mm
100mm
86g
78g
PC/ABS
White
12
Analogue Devices
CAPT340
50ºC
50ºC
65ºC
80ºC
60ºC
60ºC
77ºC
90ºC
A2S
N/A
43mm
56mm
76g
78g

Hide quick links: